6 Installation
EN
6
Installation
6.1
Connecting the Liquid Cooling Package
6.1.1
Electrical connection
General
In the supply line to the Liquid Cooling Package,
please provide the fuse specified on the rating plate
(for single-phase operation e.g. a 20 A pre-fuse), in
order to maintain the necessary protection against
short-circuits even if fully populated with four or six
fans.
Remove the access panel (fig. 38, item 1) by remov-
ing 2 Screws (fig. 38, item 2) with a T25 Screwdriver.
Fig. 38:
Access panel removal
Key
1
Access panel
2
T25 screw
3
Conduit fitting (ø 23 mm)
4
Strain relief
Install a suitable conduit fitting (fig. 38, item 3 – not
supplied) into the ø 23 mm knock-out hole at the top
of the unit.
Feed the power cable through the conduit fitting and
into the existing strain relief (fig. 38, item 4).
Note:
Please keep this electrical documentation
readily available so that it is always on hand
when needed. This is the only documenta-
tion which is authoritative for the unit.
Caution!
Work on electrical systems or equipment
may only be carried out by an electrician
or by trained personnel guided and super-
vised by an electrician. All work must be
carried out in accordance with electrical
engineering regulations.
The unit may only be connected after the
above-named personnel have read this in-
formation.
Use only insulated tools.
The connection regulations of the appro-
priate electrical power company are to be
followed.
The voltage values shown in the wiring
plan or on the rating plate must match the
mains voltage.
The pre-fuse specified in the wiring plan /
rating plate should be provided to protect
the cable and equipment from short-cir-
cuits. The unit must be individually fused.
The unit has a high discharge current. For
this reason, it is essential to make a
10 mm2 earth connection before connect-
ing to the supply circuit (see section 16.4
"Circuit diagram").
The unit must be connected to the mains
via an isolating device which ensures at
least 3 mm contact opening when
switched off.
No additional control equipment may be
connected upstream of the device at the
supply end.
Note:
The voltage tolerance must not exceed a
maximum of ±10% of the mains voltage
specified on the rating plate.
Note:
Information on the cross-section of the con-
nection cable may be found in section 16.4
"Circuit diagram".
Danger!
Take utmost care not to short-circuit one
of the phases with the zero conductor or
the earth conductor. Otherwise, there is a
risk of damage or injury.
Caution!
Only use copper supply wires.
3
2
1
4
2