Rittal HD air/water heat exchangers
13
11 Technical specifications
EN
11
Technical specifications
Observe the mains connection data (voltage and fre-
quency) as per the rating plate.
Observe the pre-fuse as per the specifications on the
rating plate.
* Stainless steel on request
Technical specifications
General specifications
Model number
3214.700
3215.700
Dimensions (width x height x depth) [mm]
220 x 526 x 100
215 x 982 x 100
Weight [kg]
6
14
Water-carrying parts
Copper/brass (Cu/CuZn)*
Temperature control
Thermostat-controlled magnetic valve
Noise level Lp [dB(A)]
<70
Cooling outputs
Cooling medium
Water (see section 13 "Hydrological data")
Water connection
⅜" cylindrical external thread
Useful cooling output [W] L35 W10, 400 l/h
0.65
1.2
Air throughput of fans (unimpeded air flow) [m³/h]
280
680
Water inlet temperature [°C]
>+1…+30
Permissible operating pressure p. max. [bar]
1…10
Operating temperature [°C]
+1…+70
Setting range [°C]
+20…+60
Electrical specifications
Type of electrical connection
Wiring on terminal strip
Rated voltage [V, ~]
230
Rated frequency [Hz]
50/60
Rated current [A]
0.16/0.14
0.38/0.47
Pre-fuse T
2
4
Power consumption P
el
33/34
77/104
Protection category
to IEC 60 529
IP 56/59
UL type
4X
Tab. 4:
Technical specifications