background image

5 Commencing operation and control behavior 

Rittal cooling unit assembly and operating instructions                                                                  page 

7

 of 

13  

 

 

Figure 5: Replacement of the filter mat 

7

 

Technical informations 

The  cooling  unit  (compressor  refrigeration  unit)  con-
sists of four main components: the coolant compres-
sor,  evaporator,  condenser,  and  the  capillary,  which 
are  connected  by  suitable  Pipe-work.  This  circuit  is 
filled with a readily boiling substance, the refrigerant. 
The  R134a  (CH2FCF3)  refrigerant  is  free  from  chlo-
rine. It has an ozone destroying potential (ODP) of 0 
and  is  therefore  environmentally  friendly.  A  filter 
dryer  which  is  integrated  in  the  hermetically  sealed 
cooling  circuit,  provides  effective  protection  against 
moisture, acid, dirt particles, and foreign bodies with-
in the cooling circuit. 

7.1.1

 

Operation of the cooling unit 

 

Figure 6: Operation of the cooling unit 

 
The  compressor  takes  the  gaseous  refrigerant  from 
the  evaporator  and  compresses  it  to  a  higher  pres-
sure  in  the  condenser.  During  this  process  the  tem-
perature  of  the  refrigerant  rises  above  the  ambient 
temperature  and  heat  can  be  dissipated  to  the  envi-
ronment  via  the  surface  of  the  condenser.  Then  the 
refrigerant  is  liquefied  and,  by  means  of  a  thermos-
tatically controlled capillary, returned to the evapora-
tor,  where  it  evaporates  at  low  pressure.  The  heat 

required  for  complete  evaporation  is  drawn  from  the 
enclosure  interior  causing  it  to  cool  down.  The  cool-
ing  cycle  is  thus  completed,  the  aforementioned 
process of the heat transfer starts afresh. 

7.1.2

 

Condensate discharge 

A  drain  pipe  fitted  to  the  evaporator  divider  panel 
ensures that any condensate which may form on the 
evaporator  (at  high  air  humidity,  low  temperatures 
inside  the  enclosure)  is  drained  away  from  the  bot-
tom  of  the  unit.  For  this  purpose,  a  length  of  hose 
should  be  fitted  to  the  condensate  pipe  connection 
piece. The condensate must be able to run off freely. 
If  the  condensate  is  to  be  drained  off  over  a  greater 
distance,  then  care  must  be  taken  that  the  hose  is 
free  from  kinks  and  a  check  for  correct  drainage 
made. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

8

 

Handling instructions 

8.1 

Fitting the cooling unit 

The enclosure cooling unit may optionally be exter-
nally mounted on the enclosure (1) or partially inter-
nally mounted (2). 
 
 
 
 
 

       

 

Summary of Contents for 1194.42 Series

Page 1: ...Assembly and operating instructions Compact cooling unit 3370 22X 3370 52X 3370 32X 3370 62X 3370 37X 3370 72X 3370 42X 1194 42X 1194 55X 1194 62X 1194 72X ...

Page 2: ... Display buttons 5 5 1 8 Compressor On Off 6 5 2 Alarm parameters 6 5 3 Evaluating system messages 6 5 4 Forced cooling 6 6 Filter mats 6 7 Technical informations 7 7 1 1 Operation of the cooling unit 7 7 1 2 Condensate discharge 7 8 Handling instructions 7 8 1 Fitting the cooling unit 7 8 1 1 External mounting of the cooling unit 8 8 1 2 Partial internal mounting of the cooling unit accessories n...

Page 3: ...ill occur if the enclosure is leaky the separation of the units from one another and from the wall should not be less than 200mm air inlet and outlet are not obstructed on the inside of the enclosure units are only fitted horizontally in the specified position Max deviation from the true horizontal 2 condensate drainage is provided electrical connection and repair are carried out only by authorize...

Page 4: ...ours C A0 Alarm and fan differential 20 20 2 See chapter 5 2 F AH Alarm maximum temp 50 99 10 See chapter 5 2 C Ad1 Delay for high and low temp alarm 0 199 30 Delay for high temperature alarm when power on just before When alarm condi tion is achieved but power on just before the timer start to count for a specify value Ad1 Only the time elapsed alarm relay can be active 5 1 3Parameter navigation ...

Page 5: ...button to access the password setting use the UP and DOWN buttons to scroll the numbers until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the pa rameters press SET to display the value associated with the parameter increase or decrease the value us ing the UP or DOWN button respectively press SET to temporarily ...

Page 6: ...emperature message may also be polled via a contact on the connection clamp of the cooling unit system message relay with changeover contact see connection diagrams Terminal 1 C connection of the supply voltage to the fault signal relay Terminal 2 NO normally open Notice Delay for high temperature alarm when power ON When alarm condition is achieved but power is ON the timer start to count for a s...

Page 7: ...of the refrigerant rises above the ambient temperature and heat can be dissipated to the envi ronment via the surface of the condenser Then the refrigerant is liquefied and by means of a thermos tatically controlled capillary returned to the evapora tor where it evaporates at low pressure The heat required for complete evaporation is drawn from the enclosure interior causing it to cool down The co...

Page 8: ...y along the back of the unit so that no gaps are left at the joints Figure 8 Applying the self adhesive tape Screw the supplied grub screws into the blind nuts on the rear of the unit Secure the unit using the supplied washers and nuts Figure 9 Securing the unit all compact units except 3370220 8 1 2Partial internal mounting of the cooling unit accessories not in cluded Fix the 4 mounting bars on ...

Page 9: ...y for use at sites with a continuous current carrying capacity incoming mains power supply of more than 100 A per phase and with a supply voltage of 400 230 V If necessary the electricity supply company must be consulted to ensure that the continuous current carrying ca pacity at the point of connection to the public grid is sufficient for connection of such a unit The fans and compressors in sing...

Page 10: ...ntensity Notice Caution Risk of fire Never use flammable liquids for cleaning Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filter if necessary Cooling membranes soiled Clean if necessary Activate test mode cooling function OK Check noise generation of compressor and fans Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filte...

Page 11: ...e 19 Twist off the screw of the outside fan 1 Figure 20 Twist off the screw of the outside fan 2 Figure 21 Remove the outside fan Figure 22 Disconnect the plug of the outside fan 1 Figure 23 Disconnect the plug of the outside fan 2 Figure 24 Clean the heat pipe and compressor chamber using compressed air ...

Page 12: ... Rittal plant Please contact us for advice 11 Scope of supply and guaran tee 1 cooling unit ready for connection 1 sealing tape 1 set of mounting and operating instructions Guarantee This unit is covered by a 1 year guarantee from the date of supply subject to correct usage see also Safety notices under heading 4 Within this period the returned unit will be repaired in the factory or replaced free...

Page 13: ...RITTAL GmbH Co KG Postfach 1662 D 35726 Herborn Phone 49 0 2772 505 0 Fax 49 0 2772 505 2319 E mail info rittal de www rittal com ...

Reviews:

Related manuals for 1194.42 Series