background image

5 Commencing operation and control behavior 

 

Rittal cooling unit assembly and operating instructions                                                                 page 

5

 of 

13  

 

 

press the SET button to access the password 
setting; use the UP and DOWN buttons to scroll 
the numbers until displaying “22” (password to 
access the parameters);  

 

press the SET button to confirm the password ; 

 

use the UP and DOWN buttons to scroll the pa-
rameters. The LED corresponding to the catego-
ry of parameters will be on (see Below Table); 

 

press SET to display the value associated with 
the parameter increase or decrease the value us-
ing the UP or DOWN button respectively;  

 

press SET to temporarily save the new value and 
display the parameter again;  

 

repeat the procedure for any other parameters 
that need to be modified;  

 

press the SET button for more than 3 s to per-
manently save the parameters and exit the pa-
rameter setting procedure. 

Accessing the type S parameters:

 

 

press SET for 1 s, the set value will start flashing; 

 

increase or decrease the value using UP or 
DOWN; 

 

press SET to confirm the new value. 

5.1.4

 

Setting the target temperature 

The temperature is preset at the factory to 35

.  

 

press SET for 1 s, the set value will start flashing; 

 

increase or decrease the value using UP or 
DOWN; 

 

press SET to confirm the new value. 

5.1.5

 

Setting the temperature range 

 

Press the SET button for  more than 3 s (if there 
are  active  alarms,  mute  the  buzzer),  the  display 
shows the parameter code “PS” (password);  

 

press  the  SET  button  to  access  the  password 
setting; use the UP and DOWN buttons to scroll  
the  numbers  until  displaying  “22”  (password  to 
access the parameters);  

 

press  the  SET  button  to  confirm  the  password; 
use  the  UP  and  DOWN  buttons  to  scroll  the  pa-
rameters. 

 

press  SET  to  display  the  value  associated  with 
the parameter increase or decrease the value us-
ing the UP or DOWN button respectively;  

 

press SET to temporarily save the new value and 
display the parameter again; 

 

 repeat  the  procedure  for  any  other  parameters 
that need to be modified;  

 

press  the  SET  button  for  more  than  3  s  to  per-
manently  save  the  parameters  and  exit  the  pa-
rameter setting procedure. 
 

 

Notice! 

It is not allowed to change the value for 
„r1 & r2“ without Rittal authorization

 

5.1.6

 

Controller display 

 

Figure 2: Controller display 

 
 

function 

Normal operation 

Start up 

no. 

on 

off 

flash 

 

compressor on 

off 

call 

on 

digits 

two digits with sign and decimal 
point, -99 to 99(*). 

 

 

Notice! 

The  parameters  that  feature  three  digit 
values  can  be  set  from  the  supervisor. 
In this case the display will show “---“

 

5.1.7

 

Display buttons 

 

Figure 3: Display buttons

 

 

no. 

Normal operation 

Start up/ reset 

Pressing the button alone 

more than 3 s: switch the 
compressor ON/OFF 

 

 

1 sec: displays/sets 
the set point 

 

more than 3 sec.: ac-
cesses the parameter 
setting menu (enter 
password 22) 

 

mutes the audible 
alarm (buzzer) 

pressed 
together (2 
and 3) acti-
vate parame-
ter reset pro-
cedure 

Start up/ reset to factory setting parameters 

 

Disconnect power supply  

 

Reconnect power supply while holding   but-

tons 2 and 3  

 

Display will show the message “CF” 

 

After a few seconds  the unit will restart with   

factory setting parameters 

Summary of Contents for 1194.42 Series

Page 1: ...Assembly and operating instructions Compact cooling unit 3370 22X 3370 52X 3370 32X 3370 62X 3370 37X 3370 72X 3370 42X 1194 42X 1194 55X 1194 62X 1194 72X ...

Page 2: ... Display buttons 5 5 1 8 Compressor On Off 6 5 2 Alarm parameters 6 5 3 Evaluating system messages 6 5 4 Forced cooling 6 6 Filter mats 6 7 Technical informations 7 7 1 1 Operation of the cooling unit 7 7 1 2 Condensate discharge 7 8 Handling instructions 7 8 1 Fitting the cooling unit 7 8 1 1 External mounting of the cooling unit 8 8 1 2 Partial internal mounting of the cooling unit accessories n...

Page 3: ...ill occur if the enclosure is leaky the separation of the units from one another and from the wall should not be less than 200mm air inlet and outlet are not obstructed on the inside of the enclosure units are only fitted horizontally in the specified position Max deviation from the true horizontal 2 condensate drainage is provided electrical connection and repair are carried out only by authorize...

Page 4: ...ours C A0 Alarm and fan differential 20 20 2 See chapter 5 2 F AH Alarm maximum temp 50 99 10 See chapter 5 2 C Ad1 Delay for high and low temp alarm 0 199 30 Delay for high temperature alarm when power on just before When alarm condi tion is achieved but power on just before the timer start to count for a specify value Ad1 Only the time elapsed alarm relay can be active 5 1 3Parameter navigation ...

Page 5: ...button to access the password setting use the UP and DOWN buttons to scroll the numbers until displaying 22 password to access the parameters press the SET button to confirm the password use the UP and DOWN buttons to scroll the pa rameters press SET to display the value associated with the parameter increase or decrease the value us ing the UP or DOWN button respectively press SET to temporarily ...

Page 6: ...emperature message may also be polled via a contact on the connection clamp of the cooling unit system message relay with changeover contact see connection diagrams Terminal 1 C connection of the supply voltage to the fault signal relay Terminal 2 NO normally open Notice Delay for high temperature alarm when power ON When alarm condition is achieved but power is ON the timer start to count for a s...

Page 7: ...of the refrigerant rises above the ambient temperature and heat can be dissipated to the envi ronment via the surface of the condenser Then the refrigerant is liquefied and by means of a thermos tatically controlled capillary returned to the evapora tor where it evaporates at low pressure The heat required for complete evaporation is drawn from the enclosure interior causing it to cool down The co...

Page 8: ...y along the back of the unit so that no gaps are left at the joints Figure 8 Applying the self adhesive tape Screw the supplied grub screws into the blind nuts on the rear of the unit Secure the unit using the supplied washers and nuts Figure 9 Securing the unit all compact units except 3370220 8 1 2Partial internal mounting of the cooling unit accessories not in cluded Fix the 4 mounting bars on ...

Page 9: ...y for use at sites with a continuous current carrying capacity incoming mains power supply of more than 100 A per phase and with a supply voltage of 400 230 V If necessary the electricity supply company must be consulted to ensure that the continuous current carrying ca pacity at the point of connection to the public grid is sufficient for connection of such a unit The fans and compressors in sing...

Page 10: ...ntensity Notice Caution Risk of fire Never use flammable liquids for cleaning Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filter if necessary Cooling membranes soiled Clean if necessary Activate test mode cooling function OK Check noise generation of compressor and fans Sequence of maintenance measures Check the level of dirt Filter soiling Replace the filte...

Page 11: ...e 19 Twist off the screw of the outside fan 1 Figure 20 Twist off the screw of the outside fan 2 Figure 21 Remove the outside fan Figure 22 Disconnect the plug of the outside fan 1 Figure 23 Disconnect the plug of the outside fan 2 Figure 24 Clean the heat pipe and compressor chamber using compressed air ...

Page 12: ... Rittal plant Please contact us for advice 11 Scope of supply and guaran tee 1 cooling unit ready for connection 1 sealing tape 1 set of mounting and operating instructions Guarantee This unit is covered by a 1 year guarantee from the date of supply subject to correct usage see also Safety notices under heading 4 Within this period the returned unit will be repaired in the factory or replaced free...

Page 13: ...RITTAL GmbH Co KG Postfach 1662 D 35726 Herborn Phone 49 0 2772 505 0 Fax 49 0 2772 505 2319 E mail info rittal de www rittal com ...

Reviews:

Related manuals for 1194.42 Series