Address
Parameter
Description
40023
Pulse Divisor
40025
Min - Reset
This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters.
Writing any other value will return an error.
40027
Max - Reset
This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max parameters.
Writing any other value will return an error.
This address is used to set
pulse divisor
of the Pulse output.
Write one of the following values to this address
for Wh
:
1
:
Divisor 1
10
:
Divisor 10
100
:
Divisor 100
1000
:
Divisor 1000 & in KWh & MWh Divisior will be
1 default.
Writing any other value will return an error.
Pulse rate divisor is set to 1, when Energy on Rs485 is set
to kWh or MWh.
40031
Analog Out 2-
Para Set
This address is used to set the parameter for Analog Output 2..
Write one of the parameter no. As per the options given in
Table 2 for Analog & Limit Output Parameters.
Writing any other value will return an error.
40037
Sys Power
System Power (Read Only) is the Nominal system power based on
the values of Nominal system volts and Nominal system current.
40039
This address is used to set the rollover count for energy. If
Energy on Rs485 is in Wh rollover count can be from 7 to 14.
If it is in KWh then rollover count can be from 7 to 12 & for MWh
rollover count can be from 7 to 9.
Energy digit
Reset Count
41