Rinnai Circ-Logic Installation And Operation Manual Download Page 10

 

Rinnai Circ

-

Logic with Grundfos GTK03 Kit

 

 

 

 

            

  

10

 

Electrical Diagram

 

Wiring Table

 

 

GTK03U 

 

(Pump)

 

Rinnai Circ

-

Logic

 

+115VAC 

 

(Circ

-

Logic)

 

Red (R) 

 

with fuse

 

Black (Bk)

 

Neutral 

 

(Circ

-

Logic)

 

Blue (Bl)

 

White (W)

 

Ground

 

Green (Gn)

 

*Connect ground to 

body of the tankless 

water heater

 

Settings for SW2 

 

(Bank Of White Switches) 

 

 

Switch 4

 

Switch 8

 

Economy Mode

 

ON

 

OFF

 

Comfort Mode

 

ON

 

ON

 

The Grundfos GTK03U Pump

s power source is 

from the tankless water heater. Disconnect this 

supply connection before servicing.

 

     WARNING

 

RISK OF ELECTRIC 

SHOCK

 

All Components Within 

Dashed Line Inside of 

 

Water Heater

 

 

Connect 

Ground to 

Tankless 

Housing

 

7.

 

Adjust the dip switch in the water heater by moving the 4th switch in the white set of switches (SW2) 

to ON.

 

• 

For Economy Mode, set the 8th switch in the white set of switches (SW2) to OFF (default). 

 

• 

For Comfort Mode, set the 8th switch in the white set of switches (SW2) to ON.

 

8.

 

Connect power to the water heater.  

 

9.

 

Press the 

On/Off

” 

button on the controller. The pump and water heater will turn on to raise the 

 

recirculation loop temperature.

 

Figure 3

 

2 Wire

 

Connector

 

Wire to 

 

tankless water 

 

heater

 

Fu
se

 

GN

 

BL

 

R

 

W

 

BK

 

GTK03U

 

Pump

 

Summary of Contents for Circ-Logic

Page 1: ...For SENSEI and non SENSEI Tankless Water Heaters...

Page 2: ...ion 6 2 1 Wiring the Pump to the Water Heater 6 2 2 Parameter Settings 7 3 Non SENSEI Installation 8 3 1 Wiring the Pump to the Water Heater 8 4 Operating the Pump 11 4 1 How It Works 11 4 2 Troublesh...

Page 3: ...Grundfos allows the user to enjoy Circ Logic with VC KB and SENSEI series tankless water heaters on a dedicated return line with the use of an external pump For all models Circ Logic operates in eith...

Page 4: ...mp In line 4 amp glass fuse included Union Set Rinnai Circ Logic Manual A licensed professional must install the GTK03U kit The installer should have the following skills Connecting gas lines water li...

Page 5: ...tion of the pump will have the terminal box located to one side of the pump or the other with the conduit entry down Figure 1A The arrows on the side or bottom of the pump housing indicate direction o...

Page 6: ...r supply to the building WARNING 1 Turn off the electrical power supply by unplugging the power cord or by turning off the electricity at the circuit breaker Remove the front panel of the water heater...

Page 7: ...g Setting Description Selection a 04 Recirculation Settings No Recirculation Recirculation Dedicated 05 Recirculation Mode1 Economy Comfort 1 Setting 05 is available only if setting 04 is selected c A...

Page 8: ...power Turn off the gas at the manual gas valve usually located immediately below the water heater Turn off the incoming water supply This can be done by turning off the water supply to the building W...

Page 9: ...or the recirculation pump is bundled with the wire harness from the PC Board the pump wiring is labeled to show where to connect to the tankless water heater The connector from the tankless water heat...

Page 10: ...before servicing WARNING RISK OF ELECTRIC SHOCK All Components Within Dashed Line Inside of Water Heater Connect Ground to Tankless Housing 7 Adjust the dip switch in the water heater by moving the 4...

Page 11: ...and the pump will turn off When the return water temperature reaches approximately 15 F 8 3 C below the temperature setting the water heater and pump will turn off The cycle will start at the approxim...

Page 12: ...Rinnai Circ Logic with Grundfos GTK03 Kit 12 Figure 5 Hot Water Outlets Check Valve Cold Water Supply Gas Supply Condensate Drain Line 3 4 in Return Line Recommended GTK03U Pump Expansion Tank...

Page 13: ...tem to be installed The drawing does not imply compliance with local building code requirements It is the responsibility of the engineer or contractor to ensure that the installation is in accordance...

Page 14: ...that the installation is in accordance with all local building codes Confer with local building officials before installation Cold Water Supply Gas Supply Hot Water Outlets Circulating Unit Non Circul...

Page 15: ......

Reviews: