POSITIONING THE HEAT PUMP
•
Arrive at site and conduct a safety audit (Safety audits can also be known as Work Method Statements
(WMS) or Job Site.
•
Analysis (JSA).
•
Park your vehicle as close as allowable to your installation. Unload all materials in a safe manner.
•
Position all materials in a convenient position near the work area.
•
The heat pump is designed to be installed outdoors or indoor if a sufficient supply of heat energy and good
ventilation is available. Good performance is obtained when the heat pump is supplied with a constant
supply of fresh air. Failure to meet above recommendations may lead to lower performance or problematic
operation of the heat pump.
•
The location
MUST
consider noise impact on living areas. Avoid positioning near bedrooms or neighbours’
bedrooms.
•
Adequate access
MUST
be available for servicing of the heat pump. Refer to clearance requirements
specified in the section ‘clearances’. The water heater must be accessible without the use of a ladder or
scaffold.
•
The water heater
MUST
not be installed in an area with a corrosive atmosphere where chemicals are
stored or where aerosol propellants are released.
•
Safely position the new unit on a level surface in accordance with all plumbing and building regulations. Use
M10 foot bolts to firmly secure the unit.
•
A properly drained overflow tray
MUST
be used where property damage could occur from water spillage.
(See AS/NZS3500.4.2 for further details.)
INSTALLATION DIMENSIONS
724
724
6-Ø 12
764
Inlet/Outlet
R1 ¼” MBSP
CHP020 Installation Dimension
INSTALLATION