Rinnai 40
Ducted Gas Heater IM
a.
Mount the networkers (refer to para 11) and connect the wiring as shown in Diagram 28.
b.
For a dual networker system to operate correctly, the networkers must be configured with one as master and one
as slave. Networkers are configured as master by default, so only the slave networker needs to be configured.
c.
Determine which networker will be the master and which will be the slave.
d.
Press Key 5 on the slave. 'Clock setting mode' displays. Confirm that the clock display is flashing.
e.
Press and hold Key 2 and Key 4 until 'Installer parameter access' displays.
f.
After the message clears, press the mode key (M) until 'n01 ID00:1' displays (refer to Diagram 29).
g.
Turn the rotary dial to change 'ID00: #' to 'ID00:
1
' (1 = master, 2 = slave).
h.
Press the on/off button to save and exit.
Note:
Installation parameters are not available from slave networkers. Therefore, after a networker is configured as a slave, the
master networker must be used to access the parameters.
Diagram 29.
Networker Identification
Networker ID
Parameter
Value
11.3.3 Change a Networker from Slave to Master
a.
Detach the networker from the backing plate. The controller powers down.
b.
While continually pressing Key 3 and Key 5:
• mount the networker onto the backing plate, and
• wait until
Set this Networker’s address!
displays.
If the message does not display, repeat from Step a.
c.
Turn the rotary dial to change 'ID00: #' to 'ID00:
1
' (1 = master, 2 = slave).
d.
Press the on/off button to save and exit.
11.3.4 Network 516 Manual
Refer to the Network 516 manual for further information about the following:
• Networker installation parameters
• Adaptive zoning
• Controlling multiple appliances with one networker
• Grouping multiple appliances into zones using one networker.
11.3.5 ZonePlus
Refer to the ZonePlus Installation Manual if installing a ZonePlus control system.