Rinnai Brivis CC315 Series Installation Manual Download Page 21

Brivis 21 

Ducted Gas Heater IM

6.1.4  Setting Fan Speed

Compact Classic Heaters are fitted with a single speed room fan with High, Medium and Low fan speed options.  

Refer to 

Section 3.6

 to change the desired fan speed. Set the fan speed to achieve, as close as possible, a 

temperature rise at the nearest outlet to the heater above the inlet (Return Air) temperature for the type of system 

as follows: 
•  Floor Outlet System: 35º to 40º C rise (e.g. Return Air temp at 20º C plus 35º C rise equals a 55º C outlet 

temperature) 

•  Ceiling or High Level outlet System: 25º to 30º C rise. If the outlet air is hotter than recommended then a higher 

fan speed should be selected to reduce the outlet temperature - and if it is lower, then reduce the fan speed 

6.2  FINAL CHECKS (COMPACT CLASSIC HEATERS)

Confirm:

•  Minimum flowing gas pressure is 1.1 kPa for natural gas and 2.7 kPa for LPG heaters with all other gas 

appliances in operation.

•  The burner pressure is as indicated on the appliance data label.
•  The temperature of the warm air at any outlet is not more than 45º C above the return air temperature.
The fan continues to run while the burners are operating.

Once Confirmed: 

•  Turn the heater OFF at the thermostat.
•  Ensure that the burners and fan turn OFF, then turn OFF the gas supply at the supply tap and remove the 

manometer hose and fitting from the pressure test point .

•  Replace and tighten the test point screw, turn ON the gas supply at the supply tap, start up the heater again and 

test for leaks using soapy water solution or a leak detector spray.

•  Replace controls access panel, then proceed to instruct the customer on correct operation of the system and 

assist the customer to fill in the Warranty Card details

•  Issue any required documentation to the relevant people/authorities in regards to the installation of the heater, 

the gas connection and power supply (for example, a Certificate of Compliance and Certificate of Electrical 

Safety).

Note: 

The temperature of the warm air at any outlet should not be more than 45º C above the return air temperature.

 

Note: 

Assist the customer with filling in the Warranty Details on the company website:

http://www.rinnai.com.au or www.brivis.com.au and follow the links.

Summary of Contents for Brivis CC315 Series

Page 1: ...Compact Classic Ducted Gas Heater Installation Manual Brivis Models CC315 CC320 CC325 CC330 by...

Page 2: ...B 276 2004 Local Regulations and Municipal Building Codes including local OH S requirements This appliance must be installed maintained and removed only by an Authorised Person For continued safety of...

Page 3: ...lations 10 3 Heater Dimensions and Clearances 11 3 1 Compact Classic 11 3 2 Service Clearances 12 3 3 Splitting Compact Classic Heaters 13 3 4 Duct Connection 13 3 5 Flue Instructions 15 3 5 1 General...

Page 4: ...ing and cooling systems Local Gas and Electricity Authorities SuperSizeGuide Building Code of Australia BCA including local OH S requirements Environment Authorities This appliance must be installed m...

Page 5: ...ions 1 2 INSTALLER DUE DILIGENCE FOR CHANGEOVERS Modern ducted gas heaters even those that are physically like for like typically have different technical specifications and control systems from exist...

Page 6: ...uctions may preclude company service personnel from being able to service the unit DISCLAIMER IMPORTANT This document is a guide only Laws regulations and industry standards can vary between States an...

Page 7: ...g and cooling systems Local Gas and Electricity Authority Codes Product Sizing Guide Local Building Regulations Environment Authorities National Construction Code of Australia NCC Note The manufacture...

Page 8: ...g to local regulations IMPORTANT Switch OFF the power and unplug the heater before touching any wiring If any electrical wiring is damaged it must be replaced by the manufacturer its service agents or...

Page 9: ...om the controls access panel side and fan motor access panel side s for the entire length of the heater The air gap created between the base of the heater and the platform by the heater s supports mus...

Page 10: ...ree ventilation area using A T x F where A minimum free ventilation area mm2 T total gas consumption of all gas appliances MJ hr e g CC320I V2 90MJ hr F factor detailed in the table below Table 1 Vent...

Page 11: ...24 168 244 407 385 615 338 386 236 485 300 300 CC320IXA V2 215 553 183 724 168 244 407 385 615 338 386 236 485 350 350 CC325I V2 215 553 183 724 168 244 407 385 615 338 386 236 485 300 300 CC325IXA V2...

Page 12: ...vertical clearance Controls Tray Position Note Heater shall be positioned in the above orientation only for service access Method 2 In Ceiling and Under Floor Diagram 5 Internal Clearances Note All m...

Page 13: ...rder 3 4 DUCT CONNECTION There are two options available for the Return Air Please refer to Diagram 7 for configuration of the unit 1 Preferred Option is Return Air on fan housing side ex factory 2 Al...

Page 14: ...he Blank Panel 2 Remove Blank Panel from the appliance 3 Insert two screws removed in Step 1 to the bottom of the Side Pop panel Blank panel Blank panel Insert screws 4 Remove the two bottom screws fr...

Page 15: ...e Flue Terminal In specific installations for example under the floor it is recommended that a remote terminal be used to terminate a horizontal flue on the outside wall of the building Please refer t...

Page 16: ...d To facilitate Add On Cooling or Fan Only operation an additional accessory ACC LOOM ADD ON RELAY CLASSIC Brivis Part No B063283 must be fitted To configure a Compact Classic heater for Add On coolin...

Page 17: ...gulations Requires Brivis programmable Thermostat Contact Brivis Technical Support for information on superseded Brivis Heaters Relay Wires PCB Wires Field Supplied Wires To Add On Cooling Unit For co...

Page 18: ...g ceiling diffusers then the return air inlet should be at a low level Ceiling systems with a high level return air may result in reduced performance Note It is important that the ducting should be w...

Page 19: ...operate efficiently with more ceiling outlets fully open if properly balanced There is not a limit maximum number of floor outlets so Table 4 lists the typical number for each heater model The outlet...

Page 20: ...e does not fall to below 1 1 kPa for natural gas and 2 7 kPa for LPG heaters This should be done with all other gas appliances operating at their full capacity j If the reading is below the minimum re...

Page 21: ...the warm air at any outlet is not more than 45 C above the return air temperature The fan continues to run while the burners are operating Once Confirmed Turn the heater OFF at the thermostat Ensure t...

Page 22: ...300 0 21 0 30 540 520 500 480 52 250 1 8 4 10 CC320I V2 90 90 19 19 300 0 21 0 30 540 520 500 480 53 315 2 5 4 10 CC320IXA V2 90 90 19 19 350 0 24 0 35 625 596 570 545 53 315 2 5 4 10 CC325I V2 107 10...

Page 23: ...Brivis 23 Ducted Gas Heater IM NOTES...

Page 24: ...ormation visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai a...

Reviews: