Rinnai Brivis 1F83C-11PRBR Installation Manual Download Page 7

Brivis 

DGH Manual Controller IM

4

Installer’s Menu #

(Hold Menu 8 Seconds) 

Description

Default Setting 

(flashing icons)

Settings 

76 

Early Start

 (starts heating or 

cooling early so your programmed 
temperature is reached by the 
programmed time)

OFF

On 

– start early 

OFF

 – start at program 

period time 

79

Fahrenheit or Celsius

 

°F

°F

 – Fahrenheit

°C

 – Celsius 

81

Temperature Display 
Adjustment 

(adjust the displayed 

“Room Temperature”)

0

-5 to +5

°

F

83

Continuous Display Light 

(keep 

the backlight always on – “C” wire 
required)

OFF

On 

 – always on

OFF

 – momentarily

 

86

Change Air Filter 

(set up a 

monthly reminder)

OFF

1 to 12

 –

  reminder  time      

                (months)

OFF

 – no filter reminder

 

99    

Keypad Lock

 (prevent unwanted 

changes to the thermostat)

OFF

On 

 – disable buttons

OFF

 – all buttons are     

             active  

INSTALLER MENU (C0ntinued)

TEST EQUIPMENT

Turn on power to the system. 

Fan Operation 

If your system does not have a G terminal connection, skip to 

Heating System

1.)

  Move fan switch to On position. The blower should begin to operate. 

2.)

  Move fan switch to Auto position. The blower should stop immediately. 

Heating System

1.)

  Move 

System

 Switch to 

Heat

 position. 

2.)

  Press   to adjust thermostat setting to 

1° 

above room temperature. The system should 

begin to operate and the thermostat will indicate 

Heat On

3.) 

Press 

 

to adjust thermostat setting 

1° 

below room temperature. The heating system 

should stop operating and the thermostat should indicate 

Heat. 

Cooling System

1.)

   Move 

System

 Switch to 

Cool

 position. 

2.) 

Press   to adjust thermostat setting 

1° 

below room temperature. The blower should 

come on immediately on high speed, followed by cold air circulation. The thermostat will 

indicate

 Cool On.

 There can be up to a 

5

 minute delay. (see INSTALLER MENU, item

 50) 

3.) 

Press   to adjust thermostat setting to 

1° 

above room temperature. The cooling system 

should stop operating and the thermostat will indicate 

Cool.  

Note: If 

Starting Soon

 is shown on the display, the compressor lockout feature is operating. 

There will be up to a 

minute delay before the compressor turns on.(see INSTALLER MENU, 

item 

50

)

CAUTION

!

To prevent compressor and/or property damage, if the outdoor temperature is below 

50°

F, 

DO NOT operate the cooling system. 

Do not allow the compressor to run unless the compressor oil heaters have been operational 

for 

hours and the system has not been operational for at least 

5

 minutes. 

TEST EQUIPMENT

Summary of Contents for Brivis 1F83C-11PRBR

Page 1: ...Brivis 1 DGH Manual Controller IM by Programmable Controller Installation Manual Model 1F83C 11PRBR Single Stage Thermostat ...

Page 2: ...GH Manual Controller IM For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer s instructions Read precautions carefully before proceeding with installation ...

Page 3: ...t Applications 4 Specifications 4 Thermostat Installation 5 Wiring 5 Precautions 5 Installer Menu 6 Test Equipment 7 Using The Thermostat 8 Thermostat Overview 8 User Menu 9 Thermostat Operation 9 Thermostat Schedule Programming 10 Troubleshooting 10 Contacts 12 ...

Page 4: ... NOTICE This product does not contain mercury However this product may replace a product that contains mercury Mercury and products containing mercury must not be discarded in household trash Refer to www thermostat recycle org for information on disposing of products containing mercury THERMOSTAT APPLICATIONS SPECIFICATIONS mV to 30VAC NEC Class II 50 60 Hz 20 to 30VAC NEC Class II 50 60 Hz 1 0 A...

Page 5: ...configuration Wiring table shown are for typical systems and describe the thermostat terminal functions WARNING Do not use on circuits exceeding specified voltage Higher voltage will damage control and could cause shock or fire hazard Do not short out terminals on gas valve or primary control to test Short or incorrect wiring will burn out thermostat and could cause personal injury and or property...

Page 6: ...NSTALLER S MENU provides access to every option while the INSTALLER S MENU press the Menu button for 8 seconds The display will show item 30 in the table below Use Next and Back to navigate through menu items Press or to change a menu setting Installer s Menu Hold Menu 8 Seconds Description Default Setting Settings Press or 30 HeatCycle Rate how often the heat will turn on MEd SLO slow MEd medium ...

Page 7: ...e System Switch to Heat position 2 Press to adjust thermostat setting to 1 above room temperature The system should begin to operate and the thermostat will indicate Heat On 3 Press to adjust thermostat setting 1 below room temperature The heating system should stop operating and the thermostat should indicate Heat Cooling System 1 Move System Switch to Cool position 2 Press to adjust thermostat s...

Page 8: ...dule 15 Day of the week used when programming a schedule 7 RaisesTemperature Setting 16 Permanent hold bypassing the schedule 8 Access Menu Options 17 Temperature setpoint 9 LowersTemperature Setting 18 Appears when the keypad is locked to prevent unwanted changes 19 Next Menu button is used to navigate within a menu 20 Access the schedule and customize thermostat features 21 Back Run button is us...

Page 9: ...ockout To prevent unwanted changes the buttons can be disabled To turn this feature On press and hold and the Menu button until the icon appears To turn Off press and hold and the Menu button for 3 seconds USER MENU To customize thermostat settings press the Menu button from the home screen Use the or buttons to highlight Settings and press Next Use Next and Back to navigate through menu items Pre...

Page 10: ...ch to OFF 3 Furnace blower compartment door panel loose or not properly installed 4 Loose connection to thermostat or system 1 Replace fuse or reset breaker 2 Turn switch to ON 3 Replace door panel in proper position to engage safety interlock or door switch 4 Tighten Connections No Heat 1 System Switch not set to Heat 2 Loose connection to thermostat or system 3 Heating System requires service or...

Page 11: ... Possible short in wiring thermostat heat cool or fan system Check each wire connection to verify they are not shorted or touching other wires Try resetting the thermostat If the condition persists contact your HVAC service person Thermostat Display Thermometer Disagree Thermostat display requires adjustment Display can be adjusted 5 See User Menu item 04 Furnace Air Conditioner CyclesToo Fast or ...

Page 12: ...iday 8 00 am to 5 00 pm EST Cost of a local call higher from mobile or public phones For further information visit www rinnai com au or email enquiry rinnai com au Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance If your appliance requires service please call our National Help Line With our policy of co...

Reviews: