Brivis
7
DGH Manual Controller IM
4
Installer’s Menu #
(Hold Menu 8 Seconds)
Description
Default Setting
(flashing icons)
Settings
76
Early Start
(starts heating or
cooling early so your programmed
temperature is reached by the
programmed time)
OFF
On
– start early
OFF
– start at program
period time
79
Fahrenheit or Celsius
°F
°F
– Fahrenheit
°C
– Celsius
81
Temperature Display
Adjustment
(adjust the displayed
“Room Temperature”)
0
-5 to +5
°
F
83
Continuous Display Light
(keep
the backlight always on – “C” wire
required)
OFF
On
– always on
OFF
– momentarily
86
Change Air Filter
(set up a
monthly reminder)
OFF
1 to 12
–
reminder time
(months)
OFF
– no filter reminder
99
Keypad Lock
(prevent unwanted
changes to the thermostat)
OFF
On
– disable buttons
OFF
– all buttons are
active
INSTALLER MENU (C0ntinued)
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System
.
1.)
Move fan switch to On position. The blower should begin to operate.
2.)
Move fan switch to Auto position. The blower should stop immediately.
Heating System
1.)
Move
System
Switch to
Heat
position.
2.)
Press to adjust thermostat setting to
1°
above room temperature. The system should
begin to operate and the thermostat will indicate
Heat On
.
3.)
Press
to adjust thermostat setting
1°
below room temperature. The heating system
should stop operating and the thermostat should indicate
Heat.
Cooling System
1.)
Move
System
Switch to
Cool
position.
2.)
Press to adjust thermostat setting
1°
below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate
Cool On.
There can be up to a
5
minute delay. (see INSTALLER MENU, item
50)
3.)
Press to adjust thermostat setting to
1°
above room temperature. The cooling system
should stop operating and the thermostat will indicate
Cool.
Note: If
Starting Soon
is shown on the display, the compressor lockout feature is operating.
There will be up to a
5
minute delay before the compressor turns on.(see INSTALLER MENU,
item
50
)
CAUTION
!
To prevent compressor and/or property damage, if the outdoor temperature is below
50°
F,
DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational
for
6
hours and the system has not been operational for at least
5
minutes.
TEST EQUIPMENT