Brivis
6
DGH Manual Controller IM
3
1.)
Gas/Elec Switch
If the system is a heat pump or electric furnace, the GAS/ELEC Switch must be set to
Elec
. If your system is a gas or oil furnace, the switch must be set to
Gas
.
2.
) O/B Terminal Switch
The O/B switch on this thermostat is factory set to the
O
position. This will accommodate
the majority of heat pump applications, which require the changeover relay to be
energized in
Cool
. If the heat pump being installed requires a
B
terminal, to energize the
changeover relay in
Heat
, the O/B switch must be moved to the
B
position.
3.)
RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not
required. If the application provides a separate wire for RC and RH, clip the RC/RH
jumper. This will isolate both terminals so they can be independently used.
INSTALLER MENU
MENU and an USER MENU. The INSTALLER’S MENU provides access to every option, while
the INSTALLER’S MENU press the
Menu
button for 8 seconds. The display will show item
30
in
the table below. Use
Next
and
Back
to navigate through menu items. Press or
to change
a menu setting.
Installer’s Menu #
(Hold Menu 8 Seconds)
Description
Default Setting Settings
(
Press or )
30
Heat Cycle Rate
(how often
the heat will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
35
Cool Cycle Rate
(how often
the cooling will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
50
Compressor Lockout
(protects the compressor
from short cycling)
OFF
On
–
5
minute display
OFF
– no delay
65
Maximum Heat Limit
(maximum set point for heat mode)
99
47
to
99
°
F
66
Minimum Cool Limit
(minimum
set point for cool mode)
45
45
to
97
°
F
74
Schedule Type
(set as either
7
-Day,
5-1-1
Day or Non-Programmable)
5
7
– 7
Day
5
– 5-1-1
Day
0
– Non Programmable
1
3
2
Premium AA alkaline batteries
are required when C-wire is
not available. When C-wire is
available, the batteries provide
a back-up source of power (this
will maintain the clock in the
event of a power outage).
INSTALLER MENU