Rinnai Australia
14
ASP Flue Installation Manual
FLUE COMPONENT ASSEMBLY
4. Fit additional lengths of ESPIPE900 as required.
5. Create the wall penetration(s) in accordance with the section “WALL PENETRATIONS” on page 6.
The minimum diameter required for wall the penetration for ESPIPE900 is 80mm.
Allow for a continuous 2° fall from the heater connection point from to the wall penetration.
6. Slide the internal wall plate supplied with ASPDFK over the length of ESPIPE900 penetrating the wall at the
internal wall end. Then pass the assembly through the internal wall penetration.
7.
Fasten the internal wall plate to the internal wall.
8. Create the wall terminal in accordance with “ASSEMBLING WALL TERMINAL ~ ASPDFK & ESPIPE900” on
page 18.
9. Move the heater into place and make the heater exhaust and combustion air hose connections in accordance
with the section “CONNECTING HEATER EXHAUST & AIR SUPPLY” on page 20.
10. Follow steps 6 through 11 from the chapter “Heater Installation” in the “Rinnai ASPIRATION Operation /
Installation Manual” supplied with the heater and complete the installation and commissioning of the heater in
accordance with these.
The joints between ESPIPE900 lengths MUST BE secured by a pop rivet or screw through the
outer co-ax pipes and flue pipes are to be clipped to the wall using the stand off clips supplied or
other suitable method. ASPKIT03 and ESPIPE900 DO NOT require cutting to be joined.
Air hose and heater exhaust connections at the energysaver heater MUST be made and checked
in accordance with these instructions. Improper connections may result in dangerous situations,
for example, the dispersion of combustion products in the space being heated.