9 Troubleshooting
9 Troubleshooting
- 50 -
<Abnormalities of Readings>
Symptoms Causes
Actions
The reading rises
(drops) and it remains
so.
Drifting of sensor
output
Perform the zero adjustment.
Presence of
interference gas
Interference gas test including solvents are identified,
and be treated properly.
Slow leak
A very small amount of the gas to be detected may be
leaking (slow leak). Because ignoring it may cause
dangers, take a remedial measure, i.e., taking actions
the same as those for the gas alarm.
Environmental
changes
Perform the zero adjustment (AIR adjustment).
A gas alarm is triggered
despite of no gas leak
and no other
abnormalities at the
detection point.
Presence of
interference gas
Interference gas test including solvents are identified,
and be treated properly.
Disturbance by
noise
Turn off and restart the detector.
If such a symptom is observed frequently, take
appropriate measures to eliminate the noise.
Sudden change in
the environment
When the environment (temperature, etc.) changes
suddenly, the detector cannot adjust to it and is affected
by it.
In some cases, the detector triggers an indication alarm.
Because the detector cannot be used under sudden and
frequent environmental changes, any preventive actions
should be taken to eliminate them by the user.
Slow response
Clogged dust filter
Replace the dust filter.
Bended, clogged, or
leaked suction tube
or exhaust tube
Fix the defective parts.
Condensation is
formed inside the
suction tube.
Fix the defective parts.
Deteriorated sensor
sensitivity
Replace the sensor with a new one.
Sensitivity calibration
impossible
Improper calibration
gas concentration
Use the proper calibration gas.
Deteriorated sensor
sensitivity
Replace the sensor with a new one.
<Abnormalities of installation environment>
Symptom/Display FAULT
Causes
Actions
Out of operating
temperature
range
E-27
―
The environmental
temperature is out of
operating temperature
range
Operating temperature range
-20 to +60
℃
If environmental temperature is out of operating
temperature range, countermeasure for
adjusting environmental temperature is needed
to be considered.
Summary of Contents for SD-1DRI
Page 1: ...PT2E 2981 Smart transmitter Gas Detector Head SD 1DRI TYPE MED EX Operating Manual PT2E 196...
Page 5: ......
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 16: ......
Page 17: ......
Page 18: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 31: ......
Page 32: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 57: ......