2 Maintenance Mode
SC-8000
- 10 -
<Alarm Setpoint Setting "ALARM-P">
Set the alarm setpoint.
ALARM-P
Press the ENTER switch.
The alarm setpoint setting selection menu is
displayed.
Press the ENTER switch. The alarm setpoint
display blinks, prompting for input.
Press the
▲
or
▼
switch to change an alarm
setpoint value. Next, press the ENTER switch to
enter it.
Set WARNING and then ALARM.
Change the last item and press the ENTER switch.
After the changed settings are confirmed and END
is displayed, the gas monitor automatically returns
to the alarm setpoint setting selection menu.
When the alarm setpoint setting is completed, press
the
▲
or
▼
switch until ESCAPE is displayed. Press
the ENTER switch to return to the maintenance
mode menu.
Return to ALARM-P.