Gas alarm operations
:
Latching (standard) or non-latching (optional)
Alarm set points
:
1st alarm “WARNING”
:
50 ppm
2nd alarm “ALARM”
:
100 ppm
(Adjustable within 20 to 200ppm as an option )
Alarm indications
:
WARNING (Yellow), ALARM (Red)
Alarm output contacts
:
No-voltage relay A contact (standard) or B contact (optional)
contact capacity
:
AC 125V 0.1mA to 0.3 A (load resistance)
Recommended cables
:
CVVS
relevant cables 1.25 to 2.0 sq
Warming up time
:
4hours (initial clear : 1 hour)
Zero suppression
:
Within 6% of the full scale
Auto zero function
:
Will aspirate zero calibration gas in set interval
Interval of operation
:
every 7 days
Operation time
:
6 minutes
Trouble (fault) alarm
Self diagnosis
:
System failure, Sensor Trouble, Zero point trouble, Lamp
trouble, Motor trouble, Heater trouble, Low flow rate, Fan
trouble
Indications
:
Flashing POWER lamp and alphabetical indications
Alarm output contacts
:
No-voltage relay A contact (standard) or B contact (optional)
contact capacity
:
AC 125V 0.1mA to 0.3 A (load resistance)
Recommended cables
:
CVVS
relevant cables 1.25 to 2.0 sq
Power source
Power voltage
:
AC 200V/ AC 220V 50/60 Hz
Power consumption
:
400V maximum
Recommended cables
:
CVVS
relevant cables 1.25 to 2.0 sq
Usage environment
Temperature
:
0 to 40
℃
Humidity
:
30 to 90 % RH (no condensations)
Structure
:
Wall mounted
Dimension
:
350(W)×440(H)×160(D)mm
(without protrusion)
Weight
:
approximately 17 kg
Colour
:
Munsell colour system 2.5Y9/2