Operating Manual
Breite: 170
Höhe:8,15
Oben Links
278,5 20
RIFOX - Hans Richter GmbH Spezialarmaturen Fon: +49 (0) 421 499 75 - 0 Internet: www.rifox.de
Bertha-von-Suttner-Str. 9 D-28207 Bremen Fax: +49 (0) 421 499 75 - 40 Email: [email protected]
Page 2 of 5
10/2020
-Di.
Subject to modifica
tions
2.2
Operation limits of housing material (Design)
max. operating pressure (bar g)
25
21
18,5
17,1
max. operating temperature (°C)
-60/100
200
300
400
2.3
Function limit of control unit
2.4
Discharge capacity
2.5 Function
■
Due to the gravity the condensate flows downwards to the lowest point, which is the condensate trap housing. In the
lowest position of the float the outlet cross-section is close. Rising of the liquid level lifts the float and opens the outlet.
Condensate will be discharged through the upturned immersion tube. Decreasing condensate level closes the outlet again.
2.6
Compensation line:
■
In order to get proper function, the non-condensable gas must be able to leave the housing. Due to the vertical instal-
lation, the non-condensable gas is able to leave the housing and flows into the steam/gas chamber above it, which has
the same pressure level. If the self-venting through the pipe must be extended, the control screw (11) can be replaced by a
cutting ring screw bolt and a compensation line can be installed leading upwards.
2.7
Automatic venting
■
In the case of steam applications, automatic venting must be provided (vent jet).
2.8
Gastight under-level float control (only for gas applications):
■
For gas applications, a gastight under-level float control is nearly exclusively used. Consult with Rifox, if necessary.
Cross Section
max. line pressure in bar g
Stream
Comp. air
Id
20
25
IId
22
25
III
13
16
IV
11
14
V
2,5
3
VI
21
25
VIa
25
25
VII
18
25
VIIIa
4
5
VIIIb
4
4,5
Picture 3