background image

Operating Manual

Breite: 170 

Höhe:8,15

Oben Links

278,5   20 

RIFOX - Hans Richter GmbH Spezialarmaturen Fon: +49 (0) 421 499 75 - 0          Internet:    www.rifox.de 
Bertha-von-Suttner-Str. 9     D-28207 Bremen Fax: +49 (0) 421 499 75 - 40         Email: [email protected]

Page 2 of 5

10/2020

-Di.

 Subject to modifica

tions

2.2 

Operation limits of housing material (Design)

max. operating pressure (bar g)

25

21

18,5

17,1

max. operating temperature (°C)

-60/100

200

300

400

2.3 

Function limit of control unit

2.4 

Discharge capacity

2.5 Function

 Due to the gravity the condensate flows downwards to the lowest point, which is the condensate trap housing. In the 

lowest position of the float the outlet cross-section is close. Rising of the liquid level lifts the float and opens the outlet. 
Condensate will be discharged through the upturned immersion tube. Decreasing condensate level closes the outlet again. 

2.6 

Compensation line: 

 

 In order to get proper function, the non-condensable gas must be able to leave the housing. Due to the vertical instal- 

 

lation, the non-condensable gas is able to leave the housing and flows into the steam/gas chamber above it, which has  

 

the same pressure level. If the self-venting through the pipe must be extended, the control screw (11) can be replaced by a  

 

cutting ring screw bolt and a compensation line can be installed leading upwards. 

2.7 

Automatic venting

 In the case of steam applications, automatic venting must be provided (vent jet).

2.8 

Gastight under-level float control (only for gas applications): 

 For gas applications, a gastight under-level float control is nearly exclusively used. Consult with Rifox, if necessary.

Cross Section

max. line pressure in bar g

Stream

Comp. air

Id

20

25

IId

22

25

III

13

16

IV

11

14

V

2,5

3

VI

21

25

VIa

25

25

VII

18

25

VIIIa

4

5

VIIIb

4

4,5

Picture 3 