Rev. 3 of 14.09.16
№
00164
3 After the Detector energizing, self-testing process is activated. The
process is accompanied by the LED indicator blinking once per second.
The LED indicator blinking red for 30 sec means a possible fault.
In case of the situation repeat after the Detector is restarted, it is
recommended to substitute the Detector.
4 The «DISARM» command ensures sound processing blocking in
order to avoid false alarm in the rooms during labor hours and to save
the battery charge. The «ARM» command transfers the Detector to
a standby mode.
5 The «Identification» command allows to find the Detector assigned
to the respective monitored zone.
Scope of Delivery
Each Detector unit package contains the items listed in Table 6.
Table 6
Description
QNT
Wireless glass break detector «CN-Glass»
Screw 3-3х30.016
CR123A lithiun power supply battery
CR2032 lithiun power supply battery
Wireless glass break detector «CN-Glass». Installation Guide
1 pc.
2 pcs.
1 pc.
1 pc.
1 copy
Storage and Transportation
1 The detectors in original package may be transported by any means
of transportation in closed vehicles over any distances in compliance
with the existing shipping rules concerning the respective means of
transportation.
2 Storage conditions of the detectors: storage premises should not
contain any current-conducting dust, acid and alkali fumes, as well
as corrosive gases or those destroying insulation.
Manufacturer’s Guarantees
«RIELTA»
JSC guarantees conformity of the Detector to it’s Technical
Specifications if conditions of transportation, storage, assembling and
operation are observed. The guaranteed storage period is 63 months
since the date of manufacturing the Detector.
The guaranteed period of operation is 60 months since the date of
commissioning within the storage period guaranteed.
For guaranteed maintenance, please contact:
«С.Nord» STCF
Russia, 190020, St. Petersburg,
Obvodny Channel emb., 199-201, build.13, BC «Obvodny Dvor»
Phone: (812) 327-16-36
E-mail: [email protected], [email protected], www.cnord.ru
Note
– Warranty obligations do not apply to the power supply
batteries.
Packing Certificate
The Detector «CN-Glass» has been manufactured in compliance
with the active technical documentation, classified as fit for operation
and packed by «RIELTA» JSC.
Packing date _______________________________
month, year
Detector Installation Examples
Correct Detector installation options see Figures 3 – 7, the incorrect one – Figure 8
Adjustment
Set the «1», «2» and «3» DIP-switches to the OFF position. Install
the power supply batteries. Estimate the interference situation in the
room (the green LED indicator should not light up).
The green indicator lighting up means the high level of interference
in the room. Remove the interference sources if possible.
Execute adjustment of the Detector as follows:
- set the «1», «2» DIP-switches to the ON position. After it shift
DIP-switch «3» to the ON position – the «Adjustment» mode is
displayted by the green LED indicator blinking once per second;
- close the cover;
- suspend a steel ball 21 – 22 mm in diameter on a 35 cm long thread
near the farthest part of the monitored glass (ordinary, ornamental,
armed, laminated), deflect it at an angle of 30 – 70° (see Table 4, 45°
for hollow glass blocks). When the green LED indicator switches on,
deliver a test blow.
Table 4
Glass thickness, mm
<3 3...4
4...5
5...6
6...7
>7
Ball deflection angle for ordinary,
armed and ornamental glass,
о
30
35
40
45
50
55
Ball deflection angle for hardened
and laminated glass,
о
45
50
55
60
65
70
In case the CP does not receive an alarm message after test blows,
the Detector sensitivity must be increased by DIP-switches «1» and
«2» (see Table 5).
Table 5
DIP-switch Position
Detector Operating Mode
1
2
3
ON
OFF
ON
OFF
OFF
ON
ON
OFF
Sensitivity (detection
range) adjustment
Decrease by 6 dB
Decrease by 12 dB
Decrease by 18 dB (min)
Max. sensitivity
OFF
ON
Standby mode
Acoustic channel setting
- this method produces the most reliable results; however, for
adjustment the Detector for monitoring a multilayer glass or a
small area of glass, it is allowed to use an AFT-100 type electronic
glass break simulator manufactured by the «DSC» company in the
«Plat/Singl» mode or an APC type glass break simulator manufactured
by the «Argus Security» company. Besides, a simulator should be used
for adjustment the Detector to multi-glazed windows;
- check the correctness of the Detector adjustment with the Detector
cover installed;
- after completing the Detector adjustment, set DIP-switch «3» to
the OFF position.
Features and Recommendations
1 The Detector backup power supply is energized whereas the main
battery is installed.
2 The LED indication is switched off automatically in 10 minutes
after the cover is closed. To restore the LED indication lighting it is
enough to open the cover.
Figure 3 – Installing the Detector
on the Ceiling
Detector
max. 6 m
Detector
Figure 5 – Installing the Detector on
the Opposite Wall
Figure 4 – Installing the Detector on
a Side Wall
min. 2 m
max. 6 m
Detector
max. 6 m
min. 2 m
Detector
min. 2 m
max. 6 m
min. 2 m
Figure 8 – Unauthorized Detector
Installation Places
Detector
max. 6 m
Figure 7 – Detector Installation
between the Glass and the Curtains
(Blinds) or on a Window Frame
Figure 6 – Installing the Detector on the Ceiling
(for window openings in the neighboring
walls monitoring)
Detector
max. 6 m
By order of «С.Nord» STCF, www.cnord.ru
Russia, 190020, St. Petersburg,
Obvodny Channel emb., 199-201, build.13, BC «Obvodny Dvor»,
Phone: (812) 327-16-36, [email protected]
Technical support: [email protected], http://support.cnord.ru
Made in Russia
The Manufacturer: «RIELTA» JSC, www.rielta.com
Russia, 197101, St. Petersburg, Chapaeva str., 17
Phone /fax: +7 (812) 233-03-02, 703-13-60, [email protected]
Technical support: phone +7 (812) 233-29-53, 703-13-57, [email protected]