WIRELESS GLASS BREAK 

DETECTOR

«CN-Glass»

Introduction

The detector «CN-Glass» (hereinafter, the Detector):
- is intended for detecting destruction of all known kinds of 

construction glass: common, quenched, patterned, armored, multilayer 
and laminated with polymer film, glass units, as well as hollow glass 
blocks installed in structural units (openings) and/or interior elements 
of closed spaces;

- transmits status messages via two-way communication in the 433.05 

to 434.79 MHz frequency range to the control panel (hereinafter, CP) 
supporting the «CN-Contact-R» wireless communication protocol;

- provides case and wall tamper protection;
- may be installed on the wall, ceiling or on a pier between the 

monitored glass and curtains;

- ensures remote monitoring of controlled glazed structures of any 

shape;

- provides multilevel microprocessor signal processing and functional 

self-test;

- adjusts the sensitivity depending on the interference situation at 

the monitored facility;

- operates at one of 4 possible operating frequencies;
- automatically switches over backup frequency in case of impairment 

of interference conditions at the main operating frequency;

- is able to switch on and off an identification and status LED indication 

by the CP relevant command.

Field of Application

The Detector can be applied in offices, shops, museums, exhibition 

halls, banks, accommodation rooms, etc.

Specifications

Table 1

Parameter

Value

Maximum detection range

6 m

Angle of coverage

120

о

Installation height

at least 2 m (see 

Figures

 3 

– 

7)

Operating temperatures range

from minus 20 to +45 °С

Relative air humidity at 25 °С

up to 90 %

Broadcast period (programmed during the 

CB binding)

10 sec to 10 min

Weight (without power batteries)

maximum 0.1 kg

Dimensions

maximum 105 x 50 x 40 mm

Battery life (under normal conditions, and 

messages transmitting period not less than 

30 sec)

up to 3 years

IP rating

IP30

Binding with the CP 

The binding procedure is intended for the logging of the Detector in 

the CP (repeater), assignment it’s number, address and the operating 

frequency chosen for this CP, initialization of the data coding system 
and exchange of service information.

1 Install the СR2032 backup power supply battery into the holder 

located on the reverse side of the Detector PCB.

2 Install the PCB into the Detector case, thereafter install the СR123А 

main power supply battery.

3 LED indicator blinking green displays the Detector readiness to the 

binding procedure.

In case of the LED indication absence, the Detector should be 

 transferred to the «Binding» mode by closing the «RESET» contacts 
until the green LED indicator starts blinking.

4 In case of successful binding with the CP (repeater), the LED 

indicator blinks red for 1 sec.

5 The binding procedure is limited up to 100 sec, whereupon the 

Detector transfers to the sleep mode. To restart the «Binding» mode 
close «RESET» contacts for a short time.

Note

 – The zone number is determined in accordance to the CP 

user manual.

Installation Guide

LED Indication

Table 2

Detector Status

Indication

«

Binding»

 

mode

LED indicator blinking green periodically

«Alarm»

LED indicator single time blinking red

«Tamper»

see section 

«

Communication Quality Appraisal

»

«Identification»

LED indicators alternate blinking red and green 

«Adjustment»

LED indicator blinking green every 1 sec under the DIP-
switch 

«

3

»

 is ON

«

Interference

»

the LED indicator lights up green

Choosing the Detector Location

Before installing the Detector, get acquainted with the following 

requirements:

- it is recommended to install the Detector at least 2 m height (see 

examples of installation in Figures 3 – 7);

- when choosing the place of installation, the Detector detection zone 

location must be taken into account (Figure 1);

- distance (L) between the Detector and the farthest point of the 

monitored glass should not exceed 6 m; 

- during joint operation with an active ultrasonic Detector, distance 

between Detectors must be not less than 1 m;

- the entire surface of the monitored glass should be available within 

the direct visibility of the Detector.

The Detector must be located within the radio visibility zone of 

it’s repeater; therefore, it is recommended to estimate the quality of 

communication with the CP (repeater).

Top View

Side View

L

L

90

о

45

о

120

о

Figure 1 – Detection Pattern

Communication Quality Appraising

To estimate the communication quality:

1 Place the Detector on it’s installation place;

2 Press the Detector tightly to a hard surface in order to close the 

tamper output;

3 Remove the Detector cover. Whereupon the Detector transmits 

a tamper message (the LED indicator lights red) and then the LED 
indicator displays communication quality with the CP by a three-grade 
scale (see Table 3).

Table 3

LED Indication

Communication 

Quality Appraisal

Recommendations

Color

Mode

Green

Three blinks

Excellent

Install the Detector at 

this place

Green

Two blinks

Good

Green

One blink

Communication 

established

Choose another place 

for installation or use a 

repeater*)

Red

Four blinks

No communication

*) – «CN-Repeater»

Installation of the Detector

Main fixation holes 
for  Detector 
installation on the 
mounting surface

Figure 2 – The Detector Base

Remove the cover and PCB 

of the Detector and fasten 
the Detector with the help of 
screws. Choose the place of 
the Detector installation and 
mark out its fastenings using 
the Detector base (Figure 2) 
for the purpose. Fix the base 
by the screws (supplied).

T o   e n s u r e   t h e   t a m p e r 

 control, the first screw should 
be screwed into the opening (1) 
at the base center, the second 
one must be screwed in a hole 
under the wall tamper (2).

Tamper clip hole

1

2