30
TECHNICAL DATA
UPS MODELS
SDH 1000
SDH 1500
SDH 2200 /
SDH 2200 ER
SDH 3000 /
SDH 3000 ER
INPUT
Nominal voltage
[Vac]
220 - 230 - 240
Maximum operating voltage
[Vac]
300
Nominal frequency
[Hz]
50 - 60
Rated current (1)
[A]
5
7
10.5 / 11.5
14 / 15
BATTERY
Recharge time (standard versions)
[h]
< 4h for 80% of the load
No. of internal batteries
3
3
6 / 0
6 / 0
Nominal voltage of battery box
36Vdc
Not
expandable
72Vdc 72Vdc
Recharge current
(only for ER versions)
Not applicable
Not applicable
6A
6A
OUTPUT
Nominal voltage (2)
[Vac]
Selectable: 220 /
230
/ 240
Frequency (3)
[Hz]
Selectable: 50, 60 or
self-learning
Nominal
power
[kVA]
1 1.5 2.2 3
Nominal power
[kW]
0.9
1.35
1.98 / 1.76
2.7 / 2.4
Overloading: 100% < load < 110%
Bypass line available:
bypass activated after 2 seconds
blocked after 120 seconds
Bypass line not available:
blocked after 60 seconds
Overloading: 110% < load < 150%
Bypass line available:
bypass activated after 2 seconds
blocked after 4 seconds
Bypass line not available:
blocked after 4 seconds
Load overload > 150%
Bypass line available:
bypass immediately activated
blocked after 1 second
Bypass line not available:
blocked after 0.5 second
OTHER DATA
Leakage current towards ground
[mA]
1
Room temperature (4)
[°C]
0 – 40
Humidity
< 90% without condensation
Protection devices
excessive battery discharge - over current - short circuit - over
voltage - under voltage - thermal
Dimensions W x D x H (5)
[mm]
87 x 425 x 450
87 x 625 x 450
Weight
[Kg]
17
18
29.5 / 14.5
31.5 / 15
For additional details regarding technical data refer to website
(1)
@ rated load, rated voltage of 220 Vac, battery charging
(2)
To maintain output voltage within the accuracy range specified, recalibration may be necessary after a long period of operation
(3)
If the network frequency is within ± 5% of the selected value, the UPS is synchronized with the network. If the frequency is out of
tolerance range or in battery operation, the frequency is that se0.1%
(4)
20 - 25 °C for longer battery life
(5)
The dimensions listed in the table refer to the tower version, taking into account the support feet.
The rack version is suitable for being housed in 19 "cabinets with an overall size of 2U