![Riello SC SUN 300 Manual Download Page 31](http://html1.mh-extra.com/html/riello/sc-sun-300/sc-sun-300_manual_1460001031.webp)
31
ENGLISH
CONTROLLER PARAMETERS TABLE
b
Observe the indications for individual parameters given on the following pages, and check whether or not further
settings are needed for the particular application.
Menu
Description
Settings range
Default
User setting
4. SETTINGS
4.1
Tmin S8
0°C ÷ 99°C
20°C
4.3
Storage priority 1
1 / 2
1
4.4
ΔT on storage 1
ΔT off storage 1
8°C ÷ 50°C
2°C ÷ 14°C
15°C
7°C
4.5
Tmax storage 1
0°C ÷ 99°C
60°C
4.6
Storage priority 2
1 / 2
2
4.7
ΔT on storage 2
ΔT off storage 2
8°C ÷ 50°C
2°C ÷ 14°C
15°C
7°C
4.8
Tmax storage 2
0°C ÷ 99°C
60°C
4.14
T-priority
0°C ÷ 90°C
40°C
4.15
Buffer time
1min ÷ 90min
20min
4.16
Increase
1°C ÷ 10°C
3°C
5. PROTECTIONS / PROTECTIVE FUNCTIONS
5.1
System protection
SP T on
SP T off
On/off
120°C ÷ 150°C
50°C ÷ 115
On
120°C
115°C
5.2
Collector protection
Collector protection on
Collector protection off
Tmax storage 1
Tmax storage 2
On/off
105°C ÷ 150°C
50°C ÷ 105
30°C ÷ 140°C
30°C ÷ 140°C
On
110°C
100°C
90°C
90°C
5.3
Recooling
Tref
On/off
0°C ÷ 99°C
On
85°C
5.4
Frost protection
Frost stage 1
Frost stage 2
On /off
6°C ÷ 10°C / off
-25°C ÷ 6°C
Off
7°C
5°C
5.5
Seizing protection R1
Seizing protection R2
Seizing protection R3
Seizing protection R4
Seizing protection R5
Seizing protection R6
Seizing protection R7
Daily / weekly / off
Off
Off
Off
Off
Off
Off
Off
5.6
Collector alarm
Collector Tmax
Delay
On/off
60°C ÷ 299°C
1min ÷ 60min
Off
115°C
1min
6. SPECIAL FUNCTIONS
6.1
Program selection
1-48
17
6.2
Speed control R1
-
-
6.2.1
Modes
M1,M2,M3,M4,off
M4
6.2.2
Type of pump 1
Standard / 0-10V /
PWM
0-10V
6.2.3
Pump menu
6.2.3.1
Pump
Solar / heating /
profile 1-11 / manual
Profile 7
6.2.3.2
Output signal
Normal / inverted
Normal
6.2.3.3
0-10 V off
0.0V ÷ 5.0V
0,7 V
6.2.3.4
0-10 V on
0.7V ÷ 5.0V
2,0 V
6.2.3.5
0-10 V max
5.0V ÷ 10.0V
10,0 V
6.2.3.6
Speed when On
10% ÷ 90%
30%
6.2.4
Purge time
5sec ÷ 600sec
8sec
6.2.5
Sweep time
1min ÷ 15 min
4min
6.2.6
Maximum speed
70% ÷ 100%
100%
6.2.7
Minimum speed
30% ÷ 95%
30%
6.2.8
Setpoint
0°C ÷ 90°C
60°C
6.3
Speed R1
-
-
6.3.1
Modes
M1,M2,M3,M4,off
M4
Summary of Contents for SC SUN 300