Installation
5.12
Electrical wiring
Notes on safety for the electrical wiring
Before carrying out any maintenance, cleaning or checking operations:
If the hood is still present, remove it and proceed with the electri-
cal wiring according to the wiring diagrams.
Use flexible cables in compliance with the EN 60 335-1 standard.
5.12.1 Supply cables and external connections
passage
All the cables to be connected to the burner should be passed
through cable grommets, as shown in Fig. 27.
The use of the cable grommets can take various forms. By way
of example we indicate the following mode:
A
Fan motor
B
Maximum gas pressure switch
C
Air servomotor
D
O
2
control
E
Air pressure switch
1
Three phase power supply with M32 cable grommet.
2
Available: single phase power supply and other devices with
hole for M20
3
Available: consents/safety, minimum gas pressure switch,
gas valves and other devices with M20 cable grommet.
4
Available: hole for M16
5
Available: hole for M20
6
Available for ground terminals
DANGER
The electrical wiring must be carried out with the electrical supply disconnected.
Electrical wiring must be made in accordance with the regulations currently in force in the country of destination
and by qualified personnel. Refer to the wiring diagrams.
The manufacturer declines all responsibility for modifications or connections different from those shown in the wir-
ing diagrams
Check that the electrical supply of the burner corresponds to that shown on the identification label and in this man-
ual.
The burner has been type-approved for intermittent use.
This means they should compulsorily be stopped at least once every 24 hours to enable the control box to per-
form checks of its own start-up efficiency. Normally, burner stopping is guaranteed by the boiler's thermostat/pres-
sure switch. If this is not the case, a time switch should be fitted in series to TL to stop the burner at least once
every 24 hours. Refer to the wiring diagrams.
The electrical safety of the device is obtained only when it is correctly connected to an efficient earthing system,
made according to current standards. It is necessary to check this fundamental safety requirement. In the event of
doubt, have the electrical system checked by qualified personnel. Do not use the gas tubes as an earthing system
for electrical devices.
The electrical system must be suitable for the maximum power absorption of the device, as indicated on the label
and in the manual, checking in particular that the section of the cables is suitable for that level of power absorp-
tion.
For the main power supply of the device from the electricity mains:
- do not use adapters, multiple sockets or extensions;
- use a multiple pole switch with at least a 3mm gap between the contacts (overvoltage category III), as envis-
aged by the present safety standards.
Do not touch the device with wet or damp body parts and/or in bare feet.
Do not pull the electric cables.
DANGER
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Avoid condensate, ice and water leaks from form-
ing.
After carrying out maintenance, cleaning or
checking operations, reassemble the hood and all
the safety and protection devices of the burner.
4
4
4
E
B
4
3
1
2
A
C
D
4
6
5
6
6
6
5
5
6
4
Fig. 27
20110412
Summary of Contents for RRS 68/E O2 BLU
Page 2: ...Translation of the original instructions ...
Page 44: ...20169327 42 GB Appendix Electrical panel layout ...
Page 46: ...20169327 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20169327 GB Appendix Electrical panel layout ...
Page 48: ...20169327 46 GB Appendix Electrical panel layout ...
Page 55: ......