27
20169327
GB
Installation
5.11.4 Gas pressure
Tab. O indicates the pressure drop of the combustion head and
the gas butterfly valve depending on the operating output of the
burner.
Tab. O
The values shown in Tab. O refer to:
–
Natural gas G 20 NCV 9.45 kWh/Sm
3
(8.2 Mcal/Sm
3
)
–
Natural gas G 25 NCV 8.13 kWh/Sm
3
(7.0 Mcal/Sm
3
)
Column 1
Load loss at combustion head.
Gas pressure measured at the test point 1)(Fig. 26), with:
•
combustion chamber at 0 mbar;
•
burner working at maximum output;
Column 2
Pressure loss at gas butterfly valve 2)(Fig. 26) with maximum
opening: 90°.
To know the approximate output at which the burner is operating
at its maximum:
–
Subtract the combustion chamber pressure from the gas
pressure measured at test point 1)(Fig. 26).
–
Find, in the Tab. O relating to the burner concerned, column
1, the pressure value closest to the result you want.
–
Read the corresponding output on the left.
Example with natural gas G 20 for RS 120/E O
2
BLU:
Maximum output operation
Gas pressure at test point 1)(Fig. 26)
=
17.0 mbar
Pressure in combustion chamber
=
3.0 mbar
17.0 - 3.0
=
14.0 mbar
A maximum output of 955 kW shown in Tab. O corresponds to
14.0 mbar pressure, column 1.
This value serves as a rough guide; the effective output must be
measured at the gas meter.
To know the required gas pressure at test point 1)(Fig. 26), set
the maximum output required from the burner operation, then:
–
find the nearest output value in the Tab. O for the burner in
question.
–
Read, on the right (column 1) the socket pressure 1)(Fig. 26).
–
Add this value to the estimated pressure in the combustion
chamber.
Example with natural gas G 20 for RS 120/E O
2
BLU:
Required burner maximum output operation: 955 kW
Gas pressure at output of 955 kW
=
14.0 mbar
Pressure in combustion chamber
=
3.0 mbar
14.0 + 3.0
=
17.0 mbar
pressure required at test point 1)(Fig. 26).
kW
1
p (mbar)
2
p (mbar)
G 20
G 25
G 20
G 25
RS 68/E O
2
BL
U
350
2,0
3,0
0,1
0,1
500
5,0
7,5
0,2
0,3
650
7,7
11,5
0,3
0,4
750
9,7
14,5
0,4
0,6
860
11,7
17,5
0,5
0,7
RS 1
20/E
O
2
BLU
600
4,4
6,6
0,3
0,4
760
9,2
13,7
0,4
0,6
955
14,0
20,9
0,6
0,9
1170
18,7
27,9
0,8
1,2
1300
22,5
33,6
1,2
1,8
WARNING
The heat output and gas pressure data in the
head refer to operation with gas butterfly valve
fully open (90°).
Fig. 26
S8716
Summary of Contents for RRS 68/E O2 BLU
Page 2: ...Translation of the original instructions ...
Page 44: ...20169327 42 GB Appendix Electrical panel layout ...
Page 46: ...20169327 44 GB Appendix Electrical panel layout ...
Page 47: ...45 20169327 GB Appendix Electrical panel layout ...
Page 48: ...20169327 46 GB Appendix Electrical panel layout ...
Page 55: ......