41
20027761
GB
Faults - Probable causes - Solutions
8.1
Light oil operation
Symbol
Problem
Possible cause
Recommended remedy
The burner does not start
Limiter or safety control device open
Adjust or replace
Control box lockout
Release
Fan motor lockout
Release the thermal relay
Intervention of maximum oil pressure switch
Adjust the pressure switch or eliminate
overpressure
No electrical power supply
Close all switches - check connections
No light oil
Check the light oil supply circuit
Control box fuse interrupted
Replace
Pump is jammed
Replace
Faulty motor remote control switch
Replace
Defective control box
Replace
Faulty electrical motor
Replace
The pilot burner does not work
Check
Defective safety solenoid valve
Replace
Faulty oil modulator
Recondition or replace it
The burner does not
switch on, and the lock-
out appears
Flame simulation
Replace the control box
Photocell short-circuit
Replace photocell
Two-phase electrical supply, thermal relay
steps in
Reset the thermal relay at return of the
three phases
The burner starts but
stops at maximum air
damper setting
Contact 1 of the servomotor terminals 9-8 con-
trol box does not intervene
Adjust cam I or replace servomotor
The burner switches on,
but then stops in lockout
Air pressure switch incorrectly adjusted
Adjust it
Pressure switch pressure point pipe blocked
Clean
The burner switches on,
but then stops in lockout
Failure to the flame detection circuit
Replace control box
The burner remains in
pre-purging phase
Contact III of the servomotor terminals 10-8
control box does not intervene
Adjust cam III or replace servomotor
Once the pre-purging
and the safety time has
elapsed the burner goes
into lockout without the
flame appearing
The VP1 solenoid lets too little gas through
Increase
The solenoid VP1 or VP2 does not open
Replace the coil or the rectifier panel
No fuel in the tank, or water on the bottom
Refill with fuel, or remove the water
Bad head and damper adjustments
Adjust
Faulty or grounded high voltage cable
Replace
High voltage cable deformed by high tempera-
ture
Replace and protect
Bad electrical wiring on valves or transformer
Check
Pump unprimed
Prime it
Pump suction line connected to return line
Correct connection
Soiled filters (nozzle line)
Clean
The valves upstream from the pump are
closed
Open them
Opposite motor rotation
Change electrical wiring to the motor
Light oil solenoids do not open
Check connections and
solenoids
Nozzle clogged, soiled or deformed
Clean it or replace it
Pilot burner does not work
Check
Defective control box
Replace
Ignition electrode incorrectly adjusted
Adjust it
Electrode grounded due to broken insulation
Replace
Motor/pump coupling broken
Replace
Faulty ignition transformer
Replace
The flame ignites regu-
larly but the burner goes
into lock out at the end of
the safety time
Faulty photocell or control box
Replace photocell or control box
Soiled photocell
Clean
P
1
Summary of Contents for RLS 650/M MX
Page 2: ...Translation of the original instructions ...
Page 50: ...20027761 48 GB Appendix Electrical panel layout ...
Page 51: ...49 20027761 GB Appendix Electrical panel layout 0 1 1 1 ...
Page 53: ...51 20027761 GB Appendix Electrical panel layout 0 0 0 ...
Page 54: ...20027761 52 GB Appendix Electrical panel layout 0 1 1 1 2 3 45678 9 55 ...