Installation
5.10
Combustion head adjustment
The adjustment of the combustion head depends only on the
maximum output of the burner.
Turn the screw 5)(Fig. 21) until the notch indicated in diagram
(Fig. 22) corresponds with the front part of the flange 6)(Fig. 21).
Example: Burner RLS 160/M MX
Burner maximum output = 1500 kW.
The diagram (Fig. 22) shows that for this output, the adjustment
of the combustion head is carried out on notch 7.
ATTENTION
To facilitate the adjustment, loosen the screw
1)(Fig. 17), adjust, then block.
Fig. 21
D1149
Fig. 22
No. of holes
Max burner output -
kW
D2996