2
(1) Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2) Sound pressure measured in manufacturers combustion laboratory, with burner operating on test boiler and at maximum rated output.
VARIANTS
ACCESSORIES
(optional):
•
RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio distur-
bance (emission of signals exceeding 10 V/m) owing to the presence
of an INVERTER, or in applications where the length of the thermostat
connections exceeds 20 metres, a protection kit is available as an
interface between the control box and the burner.
DEGASSING UNIT:
It may occur that a certain amount of air is contained in the light oil
sucked up by the pump. This air may originate from the light oil itself as
a consequence of depressurization or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in
single-pipe systems, the air remains in circulation causing pressure varia-
tions in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner
in single-pipe installations.
Degassing units are provided in two versions:
CODE
3010054
without filter
CODE
3010055
with filter
- Burner delivery
: max. 80 kg/h
- Light oil pressure
: max. 0.7 bar
- Ambient temperature
: max. 50 °C (without filter)
- Ambient temperature
: max. 40 °C (with filter)
- Light oil temperature
: max. 50 °C (without filter)
- Light oil temperature
: max. 40 °C (with filter)
- Attachment connectors
: 1/4 inch
For burner deliveries higher than 80 kg/h, install two parallel degassing
units
TECHNICAL DATA
MODEL
RL 130
TYPE
57368X
OUTPUT
(1)
DELIVERY
(1)
2nd stage
kW
Mcal/h
kg/h
948 - 1540
816 - 1325
80 - 130
1st stage
kW
Mcal/h
kg/h
486 - 948
418 - 816
41 - 80
FUEL
Light oil
- Net calorific value
kWh/kg
Mcal/kg
11.8
10.2 (10.200 Kcal/kg)
- Density
kg/dm
3
0.82 - 0.85
- Viscosity at 20 °C
mm
2
/s max
6 (1.5 °E - 6 cSt)
OPERATION
• Intermittent (min. 1 stop in 24 hours)
• Two-stage (high and low flame) and single-phase (all - nothing)
NOZZLES
numer
2
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATURE
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
3 ~ 220 - 380 V - 60 Hz
1N ~ 220 V - 60 Hz
AUXILARY CIRCUITS SUPPLY
V
220-230
ELECTRICAL MOTOR
rpm
W
V
A
3500
2200
220 - 380
8.1 - 4.7
IGNITION TRASFORMER
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1.9 A - 30 mA
PUMP
delivery (at 12 bar)
pressure range
fuel temperature
kg/h
bar
°C max
176
10 - 20
60
ELECTRICAL POWER CONSUMPTION
W max
2600
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
2004/108 - 2006/95 - 2006/42
NOISE LEVELS
(2)
dBA
78.5
Model
Code
Electrical
supply
Blast tube
lenght mm
RL 130
20057368
Three-phase
250
385
BURNER
RL 130
Code
3010386