13
20136874
GB
Installation
5.4
Preliminary checks
Checking the consignment
Checking the characteristics of the burner
Check the identification label of the burner, showing:
the model
A
)
B
);
the year of manufacture, in cryptographic form
C
);
the serial number
D
);
the electrical power consumption
E
);
the types of fuel used and the relative supply pressures
F
);
the data of the burner's minimum and maximum output pos-
sibilities
G
) (see Firing rate).
5.5
Operating position
CAUTION
After removing all the packaging, check the integ-
rity of the contents. In the event of doubt, do not
use the burner; contact the supplier.
The packaging elements (wooden cage or card-
board box, nails, clips, plastic bags, etc.) must not
be abandoned as they are potential sources of
danger and pollution; they should be collected and
disposed of in the appropriate places.
WARNING
The output of the burner must be within the
boiler's firing rate.
WARNING
A burner label that has been tampered with, re-
moved or is missing, along with anything else that
prevents the definite identification of the burner
makes any installation or maintenance work diffi-
cult.
Fig. 5
D9370
WARNING
The burner is designed to work only in positions
1
and
2
Installation
1
(Fig. 6) is preferable, as it is the only
one that allows the maintenance operations as
described later in this manual.
Installation
2
(Fig. 6) allows it to operate but not
maintenance with hooking to the boiler.
Any other position could compromise the correct
operation of the appliance.
WARNING
Any other positioning could compromise the cor-
rect operation of the appliance.
Installations
3
,
4
and
5
(Fig. 6) are prohibited for
safety reasons.