background image

5831

10

SPRAY TEMPERATURE ADJUSTMENT

Thermostat for adjustment - maximum value - minimum value

Electronic adjustment thermostat By means of information relayed from a PT100 probe immersed in the oil in the
delivery manifold, the thermostat adjusts spray temperature. (The correct conditions for fuel spray are shown in the
temperature/viscosity graph below).

Example: fuel oil with 7 °E viscosity at 50 °C is pre-heated to approximately 110 °C.

Note:

 although the temperature set on the thermostat should correspond to the temperature of the fluid, it is good

practice to check that the thermometer shows the correct reading once the unit has been in operation for a few
minutes.
The LED will illuminate to indicate that the heating resistances are working properly.

Minimum temperature thermostat. In addition to shutting down the burner if the fuel temperature should fall below the
critical value for correct combustion, this thermostat also provides a permissive signal at the time of burner start-up.
(Factory set at approximately 80°C, adjustable by removing the pre-heater cover and relative plate).

Maximum temperature thermostat. This switches off the resistance when, because of failure of the adjustment ther-
mostat, the temperature of the pre-heater increases to unacceptable levels; a “high temperature” alarm output is
provided on the burner terminal strip. (Factory setting is approximately 180°C).

Renewing the minimum and maximum temperature thermostats.
Reposition the probes of the new thermostat, after having first loos-
ened the plate pack securing screws. Make sure that the probe is
touching the resistance and the plate pack as shown in the adjacent
figure. The same precautions should be taken when renewing the re-
sistances in contact with the thermostat probes.
If the pre-heater should malfunction, use an ohmmeter to check that
the resistances located in contact with the temperature probes are not
burnt out (reading of approximately 35 Ohm).

Changing the PT100 probe in the oil delivery manifold:
Fit the supplied nut and biconical collar on the new probe, insert a
length of approximately 40 mm in the manifold, and secure firmly into place.
At this point, the section remaining outside the manifold can be bent as required, with no risk of damaging the re-
sistance.

Atomisation temperature

Viscosit

y

 at 50°C

mm

2

/s °E

Max. temperature thermostat

Adjustment thermostat probe

Thermometer

Min. temperature thermostat

Pre-heater

Purge

Thermostat probe

Resistance

Tubes into aluminium plate

Aluminium
plate

Summary of Contents for PRESS 140 T/N ECO

Page 1: ...Installation use and maintenance instructions 2915831 4 11 2012 Heavy oil burners CODE MODEL TYPE 3436885 PRESS 140 T N 466 T80 3436886 PRESS 140 T N 466 T80...

Page 2: ...r Output 320 1600 kW 28 140 kg h See page 3 Operation 1st stage 2nd stage 3rd stage Fuel Oil with max viscosity 50 mm2 s 7 E at 50 C with kit max viscosity 500 mm2 s 65 E at 50 C Pump 350 kg h at 25 b...

Page 3: ...are improved and no problems arise Boiler front plate drilling Combustion head projection For the combustion head projection carefully follow the boiler manufacturer indications A proper protection w...

Page 4: ...st STAGE POWER AND OUTPUT MINIMUM MAXIMUM kW kg h kW kg h 1st nozzle ignition phase 262 23 536 47 1s t 2nd nozzle intermediate phase 536 47 1060 93 1s t 2nd 3rd nozzle operation phase 798 70 1595 140...

Page 5: ...the burner pump If several burners are supplied through the same ring supply line the forwarding pump should have a capacity of approx 30 more than the sum of the single burners outputs For starting u...

Page 6: ...Maximal thermostat FR Photoresistance Tm Minimal thermostat MB Burner terminal strip TP Timer MV Fan motor L1 Lamps for 1 stage RMO Control box L2 Lamps for 2 stage RT Overload L3 Lamps for 3 stage S...

Page 7: ...f wiring connecting the thermostat exceeds 20 metres in length or in places where the burner is subject to particularly disturbing electromagnetic interference over 10 v m you must insert the relay in...

Page 8: ...es Nozzles 60 Pump pressure 25 bar The references of table B should be followed in case of need of modification of the pump pressure in order to vary the output diverse composition of the 3 nozzles gr...

Page 9: ...e real delivery against the rated one The pump leaves the factory set at 25 bar On the base of the maximum delivery detect from table C the combustion head adjustment The adjustment should be made by...

Page 10: ...axis It maintains the shutters of 2nd and 3rd stage closed during the 1st stage operation and in the stop periods Do not turn clockwise the lever to avoid crawlings of the air shutters turning the lev...

Page 11: ...tance when because of failure of the adjustment ther mostat the temperature of the pre heater increases to unacceptable levels a high temperature alarm output is provided on the burner terminal strip...

Page 12: ...ttings Motor lock out It is caused by the over load relay when overload oc curs or no current supply Re set push button 7 and 10 fig 1 NB Periodically clean the filter of the pre heater tank THREE STA...

Page 13: ...ow Green Red RED LED on wait at least 10 s Press button for 3 s Signal Signal Interval 3 s In the event of a burner lockout more than two conse cutive burner reset operations could cause damage to the...

Page 14: ......

Page 15: ......

Page 16: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www rielloburners com...

Reviews: