UPS
CONFIGURATION
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Language*
Selects mimic panel
language language
English
English
Italian
German
French
Spanish
Polish
Russian
Chinese
Output voltage
Selects the rated output
voltage
(Phase - Neutral)
230V
220V
230V
240V
Buzzer
Selects the audible alarm
operating mode
Reduced
Normal
Reduced: does not sound due to the
momentary intervention of the bypass
Operating mode**
Selects one of five different
operating modes
ON LINE
ON LINE
ECO
SMART ACTIVE
STAND-BY OFF
Battery low **
Estimated autonomy time
remaining for “battery low”
warning
3 min.
1
÷
7 @1 min step
Date and time**
UPS internal watch setup
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
Configurations which can be modified by means of configuration software available at service centres are listed in the following
table.
FUNCTION
DESCRIPTION
DEFAULT
Operating mode
Selects one of five different operating modes
ON LINE
Output voltage
Selects the rated output voltage
(Phase - Neutral)
230V
Output nominal frequency
Selects the rated output frequency
50Hz
Autorestart
Waiting time for automatic power-on after the return of mains
voltage
5 sec.
Auto power off
Automatic UPS power-off in battery operation mode if the
charge is lower than 5%
Disabled
Buzzer Reduced
Selects the audible alarm operating mode
Reduced
EnergyShare off
Selects the auxiliary socket operating mode
Always connected
Timer
Programmed UPS power on/off (daily)
Disabled
Autonomy limitation
Maximum battery operation time
Disabled
Maximum load
Selects the user overload limit
Disabled