3
2915386
GB
LPG kit
2.4
Combustion head setting
Air setting
, screw 1)(
A
- Fig. 2): unchanged.
Gas setting
, disc 1)(
B
- Fig. 2): always set on 0.
2.5
Gas pressure - output
Pressure measured at the coupling 2)(
A
- Fig. 2) with combustion
chamber at 0 mbar and burner in 2
nd
stage operation.
If the combustion chamber is pressurized, the required gas-pres-
sure is that shown on the diagram plus the pressurization value.
2.6
Combustion chamber pressure
The combustion chamber pressure is the same as for natural
gas.
Fig. 2
D1303
A
B
D1316
G
as p
res
sur
e (m
ba
r)
Output
809 T1 - 824 T1
811 T1 - 826 T1
810 T1 - 825 T1
Fig. 3
WARNING
For pressure levels different from those indicated
above, please contact the Technical Office.