2915386
2
GB
LPG kit
2.1
Kit description
The kit allows the burners designed to work with natural gas to
burn LPG. The kit is composed of:
(*)
LPG kit with butane amount over 30%.
2.2
Technical features
2.3
Conversion
Proceed as follows:
On the combustion head: replace the distributor 1), by that sup-
plied for LPG 2) and do the same for ionisation 3) and ignition 4)
electrodes (Fig. 1).
2
LPG kit
Description
Quantity
Distributor assembly
1
Ionisation probe
1
Ignition electrode
1
Label
1
Instruction
1
WARNING
Apply the self-adhesive label for LPG operation
near the characteristics label.
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
Model
Code
*
Type
RS 28 - RS 28/m
3010079 - 3010080
809 T1 - 824 T1
RS 38 - RS 38/M
3010081 - 3010082
810 T1 - 825 T1
RS 50 - RS 50/M
3010083 - 3010084
811 T1 - 826 T1
Burner
RS 28 - RS 28/M
RS 38 - RS 38/M
RS 50 - RS 50/M
Type
809 T1 - 824 T1
810 T1 - 825 T1
826 T1 - 826 T1
Max. burner output
kW
Mcal/h
163 - 325
140 - 280
232 - 440
200 - 378
295 - 600
254 - 516
Min. burner output
kW
Mcal/h
81
70
105
90
115
99
Minimum gas pressure
mbar
In order to have the maximum burner output, it is necessary:
11.5
13
10.5
measured at the pipe coupling, with combustion chamber at 0 mbar and gas with Net cal-
orific value = 22,200 kcal/m
3
Maximum gas pressure
mbar
100
Fuel
Commercial LPG (C
3
H
8
= 93 - 94%)
Net calorific value = 25.8 kWh/Nm
3
- 22.200 kcal/Nm
3
DANGER
disconnect the electrical supply from the burner by
means of the main system switch.
WARNING
Electrode setting: 2 mm behind the disc and near
the upper small tube.
Fig. 1
D1302
1
2
PROBE