0MNUOC1RUA_GB (614-06498-00)
1 -
T
ECHNICAL
S
PECIFICATIONS
MODELS
Dialog Plus 70
Dialog Plus 100
Dialog Plus 100 ER
INPUT
Nominal voltage (±1.5%)
[Vac]
220 / 230 / 240
Transfer Voltage Range
- low line transfer
[load %]
[Vac]
Based on load percentage
100-80% =160 ± 5
80-70% = 140 ± 5
70-60%= 120 ± 5
60-0%= 110 ± 5
-Low line comeback
[Vac]
170 ± 5
-High line transfer
[Vac]
300 ± 5
-High line comeback
[Vac]
285 ± 5
Nominal frequency
[Hz]
50 / 60
Nominal current
[A]
3.8
5
6.2
Power factor
≥
0.97
Input protection
7A thermal breaker
BYPASS
Accepted voltage range for switch over
[Va
c]
180 - 264
Accepted frequency range for switch over
Selected frequency ±5 %
Time taken for switch over
[msec]
Typically: 2 - Maximum: 4
BATTERY
N° batteries / V / Ah
2 / 12 / 7.2
3 / 12 / 7.2
--
Recharge time
[h]
4 h to 80% of full charge
--
OUTPUT
Nominal voltage
[Vac]
220 / 230 / 240
Static variation (4)
1.5%
Dynamic variation (5)
≤
5% in 20 msec
Wave form
Sinusoidal
Voltage distortion @ linear load
≤
3%
Voltage distortion @ distorting load (3)
≤
6%
Frequency (6)
50 – 60 Hz ± 0.2Hz
Synchronisation range
46-54Hz / 56-64Hz
Current crest factor
3 : 1
Nominal power (3)
[VA]
700 1000
Nominal power
[W]
490 700
OTHER VALUES
Current leakage to ground
[mA]
≤
1.2
AC/AC efficiency
86% 88%
Ambient temperature (7)
[°C]
0 – 40
Humidity
< 90% non condensing
Protections Excessive
battery
discharge - overcurrent – short circuit –
overvoltage - undervoltage - thermal
Safety certifications
EN62040-1-1 and EEC 73 / 23, 93/68 specifications
EMC Compliance
EN 50091 - 2 cl. B and EEC 89/336, 92/31, 93/68 specifications
Noise
< 45 dB(A) at 1 Mt.
Dimensions H x W x D
[mm]
231 x 158x 400
Weight [Kg]
12 14 8