9
20168415
GB
Technical description of the burner
4.3
Burner categories
Tab. B
4.4
Technical data
Tab. C
(1)
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2)
Pressure at the test point of the pressure switch (Fig. 26 on page 26) with zero pressure in the combustion chamber and at maximum burner output.
(3)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output. The sound
power is measured using the "Free Field" method, required by EN 15036 standard, and according to an “Accuracy: Category 3” measurement, as
described in EN ISO 3746.
4.5
Electrical data
Tab. D
Country of destination
Gas category
BE
I2E(R)
LV
I2H
CY, MT
I3B/P
BE
I3P
LU, PL
II2E3B/P
DE
II2ELL3B/P
FR
II2Er3P
AT, CH, CZ, DK, EE, FI, GR, HU, IS, IT, LT, NO, RO, SE, SI, SK, TR
II2H3B/P
ES, GB, IE, PT
II2H3P
NL
II2EK3B/P
Model
RS 25/M BLU
RS 35/M BLU
Output
(1)
Max.
kW
Mcal/h
125 ÷ 370
108 ÷ 320
202 ÷ 480
174 ÷ 413
Min.
kW
Mcal/h
45
39
70
60
Fuel
Natural gas: G20 - G25
Pressione gas alla potenza max.
(2)
Gas: G20 / G25
mbar
15.6 / 21.8
15.6 / 23.3
Operation
•
Continuous (min. 1 stop in 72 hours).
•
This burner is also suitable for intermittent operation, only with the use of
the UV flame sensor kit.
Standard applications
Boilers: water, steam, diathermic oil
Ambient temperature
°C
0 - 40
Combustion air temperature
°C max
60
Noise levels
(3)
Sound pressure
Sound power
dB(A)
68
79
70
81
Model
RS 25/M BLU
RS 35/M BLU
Main electrical supply
230V ~ +/-10%
50/60Hz single phase
230V ~ +/-10%
50/60Hz single phase
Fan motor
rpm
V
W
2800
230
300
2800
230
420
Acceleration current
A
14.9
16
Operating current
A
2.4
2.6
Motor capacitor
µF
12.5/260
12.5/420
Ignition transformer
V1 - V2
I1 - I2
230 V - 1 x 15 kV
1 A - 25 mA
230 V - 1 x 15 kV
1 A - 25 mA
Absorbed electrical power
W max
720
820
Protection level
IP 40