Riello 40 FS5D Installation, Use And Maintenance Instructions Download Page 37

35 

20146103

GB

Maintenance

Fan

Check that the air damper is positioned correctly.
Check to make sure that no dust has accumulated inside the fan
or on its blades, as this condition will cause a reduction in the air
flow rate and provoke polluting combustion.

Boiler

Clean the boiler as indicated in its accompanying instructions in
order  to  maintain  all  the  original  combustion  characteristics  in-
tact, especially the flue gas temperature and combustion cham-
ber pressure.

Gas train

Check that the gas train is suited to the burner capacity, the type
of gas used and the mains gas pressure.

Electrode-probe

Checking the proper positioning of the ionisation probe and elec-
trode as shown in Fig. 11 on page 15. 

Pressure switches

Check that the air pressure switch and the gas pressure switch
are set correctly.

Gas leaks

Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.

Gas filter

Change the gas filter when it is dirty.

Combustion

If the combustion values measured before starting maintenance
do not comply with applicable legislation or do not indicate effi-
cient combustion, consult the Tab. O on page 33 or contact our
Technical  Support  Service  to  implement  the  necessary  adjust-
ments.
Leave the burner working without interruption for 10 min., check-
ing the right settings at 1st and 2nd stage of all the components
stated in this manual. 

Then carry out a combustion check verifying:

Percentage of CO

2

 (%)

CO content (ppm)

NOx content (ppm)

Ionisation current (µA)

Smoke temperature at the flue

7.2.4

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. P. The specified life cycles do not refer to
the  warranty  terms  indicated  in  the  delivery  or  payment
conditions.

Tab. P

7.3

Opening the burner

If maintenance of the combustion head is required, refer to the in-
structions given in “Operating position” on page 14.
For accessing to the interior of the burner, loosen the screws that
secure the cover and proceed with the maintenance operation.

Check the operation

Start-up  of  the  burner  with  a  sequence  of  functions  (see
chapter “Operating programme” on page 22)

Ignition device

Air pressure switch

Flame monitoring

Tightness test of components to the passage of fuel

Safety component

Life cycle

Flame control

10 years or 250,000

operation cycles

Flame sensor

10 years or 250,000

operation cycles

Gas valves (solenoid)

10 years or 250,000

operation cycles

Pressure switches

10 years or 250,000

operation cycles

Pressure adjuster

15 years

Servomotor (electronic 
cam) (if present)

10 years or 250,000

operation cycles

Oil valve (solenoid)(if 
present)

10 years or 250,000

operation cycles

Oil regulator (if present)

10 years or 250,000

operation cycles

Oil pipes/ couplings 
(metallic) (if present)

10 years

Flexible hoses (if present)

5 years or 30,000 pressurised 

cycles

Fan impeller

10 years or 500,000 start-ups

DANGER

Disconnect  the  electrical  supply  from  the  burner
by means of the main system switch.

DANGER

Turn off the fuel interception tap.

Wait  for  the  components  in  contact  with  heat
sources to cool down completely.

DANGER

Operating safety hazards

Repairs to the following components may only be
carried out by the respective manufacturers or by
personnel instructed by them:

fan motor

actuator

air damper servomotor

electromagnetic valves

burner programmer

After  carrying  out  maintenance,  cleaning  or
checking  operations,  reassemble  the  cover  and
all the safety and protection devices of the burner.

Summary of Contents for 40 FS5D

Page 1: ...Installation use and maintenance instructions 20146103 2 09 2018 Forced draught gas burner Two stage operation CODE MODEL TYPE 3758705 RIELLO 40 FS5D 587M GB...

Page 2: ...Translation of the original instructions...

Page 3: ...minary checks 14 5 4 1 Control of the supply 14 5 4 2 Control of burner characteristics 14 5 5 Operating position 14 5 6 Securing the burner to the boiler 15 5 6 1 Hinge installation 15 5 7 Positionin...

Page 4: ...e menu 29 5 14 3 Shut down test 30 5 14 4 Post purging and continuous purging 30 5 14 5 Intermittent operation 30 5 14 6 Setting the opening delay of the 2nd stage 30 5 14 7 Setting a long pre purging...

Page 5: ...and according to the European Directives GAR 2016 426 EU Gas Appliances Regulation MD 2006 42 EC Machine Directive LVD 2014 35 EU Low Voltage Directive EMC 2014 30 EU Electromagnetic Compatibility Suc...

Page 6: ...ed out correctly may cause damage to the ma chine and or injury to people DANGER DANGER LIVE COMPONENTS This symbol indicates operations which if not car ried out correctly lead to electric shocks wit...

Page 7: ...vent of damage to things or injury to people if such damage injury was due to any of the following causes incorrect installation start up use and maintenance of the burner improper incorrect or unreas...

Page 8: ...intenance Only those parts envisaged by the manufacturer can be replaced 3 2 Personnel training The user is the person body or company that has acquired the machine and intends to use it for the speci...

Page 9: ...Fuel Natural gas Light oil LPG Variations Electrical supply of the system 1 230 50 1 230 60 F S 5 1 230 50 BASIC DESIGNATION EXTENDED DESIGNATION 1 230V 50Hz 1 230V 60Hz Light oil Natural gas K Conic...

Page 10: ...are given in Fig 1 Model RIELLO 40 FS5D Type 587 M Heat output Hi 1 min max kW kcal h 12 23 58 10 000 20 000 50 000 Fuel Family 2 NCV 8 12 kWh m3 7 000 10 340 kcal m3 Pressure min 8 mbar max 200 mbar...

Page 11: ...the manufacturers 4 7 Correlation between gas pressure and burner output To obtain the maximum output Fig 3 it is necessary to have 4 6 mbar measured on the pipe coupling with the combustion cham ber...

Page 12: ...Electrode probe 16 Air damper opening motor 17 4 pole socket for 2nd stage 4 9 Burner equipment Screws with nuts No 4 Insulating gasket No 1 Cover fixing screw No 3 Cable grommet No 1 Hinge No 1 7 pi...

Page 13: ...the control box from the burner it is necessary to Fig 5 disconnect all the connectors connected to it all the plugs the high voltage cables and the earth wire TB unscrew the screw A and pull the cont...

Page 14: ...anner and correctly fix the cover Check the wiring is in order Falls and collisions can negatively affect the safety func tions In this case the servomotor must not be operated even if it displays no...

Page 15: ...r If the smoke pipe is closed the burner must be drawn back till the extraction of blast tube from the furnace Before oper ating in this way take the voltage off 5 3 Handling The transport weight is g...

Page 16: ...must not be abandoned as they are potential sources of danger and pollution they should be collected and disposed of in the appro priate places WARNING A burner label that has been tampered with re m...

Page 17: ...ner WARNING Boiler door must have a max thickness of 80 mm refractory lining included If the thickness is great er max 105 mm a combustion head extension should be used to be requested separately S739...

Page 18: ...st proceed as follows Take the burner to the 2nd stage The mobile air damper 1 Fig 14 activated by the motor 2 ensures the suction inlet opens completely Adjust 2nd stage air delivery using the fixed...

Page 19: ...EN 676 and provided separately from the burner Supplied separately for its adjustment see the enclosed instructions The train burner combination is indicated in Tab F Tab F Explosion danger due to fue...

Page 20: ...ig 4 on page 10 of the burner DANGER Disconnect the electrical power using the main switch Check that there are no gas leaks Pay attention when handling the train danger of crushing of limbs Make sure...

Page 21: ...on a cycle arrest must be ensured within 24 hours with the use of a time switch positioned in series with the thermostatic line Refer to the wiring diagrams The electrical safety of the device is obta...

Page 22: ...electrical supply of the burner corresponds to that shown on the identifica tion label and in this manual The section of the conductors must be at least 1mm2 Unless requested otherwise by local standa...

Page 23: ...1st stage hour counter h2 2nd stage hour counter PG Min gas pressure switch S3 Remote lock out signal 230V 0 5A max T6A Fuse TL Limit thermostat TR 2nd stage thermostat TS Safety thermostat VPS Valve...

Page 24: ...5 Delay time between the 1st and 2nd stage ts Safety time V1 1st stage valve V2 Valve 2nd stage t2 t1 t3 t4i ts HT FM ID V1 LED P M LED t4l PG P TR P M AD t5 V2 SO SO POWER SUPPLY Signal not requested...

Page 25: ...5 t3r A recycle attempt is made if there is an air pressure drop during the pre purging stage there is then a lockout in the event of a second loss of air pressure between the 16th second and the 29th...

Page 26: ...s flame loss during operation RED fast blinking 0 2 0 2 Lockout due to a drop in air pressure after the pre purging was repeated due to a previous lack of air or 10 sec before the end of the pre purgi...

Page 27: ...the flame goes out and the start up sequence restarts If the switch off test is enabled the number of repetitions of the start up sequence see paragraph Recycle and limit of repeti tions on page 25 an...

Page 28: ...paragraph Fault diagnostics lockouts on page 24 The burner restarts when the voltage is exceeds approx 170V or is brought back under 270V If the fault is detected with flame operation the valve is im...

Page 29: ...t for a pre set time The burner switches off the flame when the heat request thermostat opens cutting off the fuel sup ply to the valves The post purging function is not performed after a lockout of t...

Page 30: ...with the operating hours also the number of the burner s first stage valve openings is saved In the menu see paragraph Programming menu on page 29 it is possible to independently reset both the opera...

Page 31: ...the menu Switching off test 5s t 10s 2 blinks RED none none Automatic at the end of the blink Post purging Continuous purging 10s t 15s 1 GREEN blink 1 1 minute 2 2 minutes 3 3 minutes 4 4 minutes 5 5...

Page 32: ...e button GREEN led OFF Press the button 1 time to enable a shut down every hour Press the button 2 times to enable a shut down every 24 hours GREEN led ON and OFF every time press and release After 10...

Page 33: ...setting the programming menu parameters and the lockout log The control box allows you to reset the log and the number of lockouts the operating hours the number of ignitions and recov er the menu s d...

Page 34: ...st or af ter a recycle due to flame loss during operation After 15 seconds the air pressure is too low the head has been poorly adjusted The air pressure switch is defective change it Lockout for loss...

Page 35: ...the knob anticlockwise to an extent that is around 20 of the adjusted value and then check that the burner starts up properly If the burner locks out again turn the knob slightly in an anticlock wise...

Page 36: ...ls or close open position indicator that turn on at the same time as their power supply 7 2 3 Checking and cleaning Combustion Check there are no occlusions or obstructions in the fuel supply or retur...

Page 37: ...P The specified life cycles do not refer to the warranty terms indicated in the delivery or payment conditions Tab P 7 3 Opening the burner If maintenance of the combustion head is required refer to t...

Page 38: ...Adjust them The connections in the control box are wrongly inserted Check and connect completely all the plugs The air pressure switch is changed over to the operational position Replace the pressure...

Page 39: ...mmedi ately and the motor stops The pressure then starts to increase again the pressure switch closes the start up cycle be gins again and so on Lower and set the pressure switch Faults Possible Cause...

Page 40: ...g kit Gas trains in compliance with EN 676 Please refer to manual A Appendix Accessories Burner Standard length mm Long head length mm Code RIELLO 40 FS5D 100 125 3000820 Burner Projection mm Code RIE...

Page 41: ......

Page 42: ......

Page 43: ......

Page 44: ...Subject to modifications RIELLO S p A I 37045 Legnago VR Tel 39 0442 630111 http www riello it http www riello com...

Reviews: