1718
1
GB
Oil burner
G20
I
CODE
3748410
TYPE
484T1
TECHNICAL FEATURES
◆
For use on hot air generator the burner must be fitted with control box type 479SE or
539SE.
◆
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 98/37/EEC and Efficiency 92/42/EEC.
◆
The burner meets protection level of IP 40, EN 60529.
◆
CE Certification No. : 0036 0259/99 as 92/42/EEC.
Thermal power – output
71 / 95 – 240 kW
–
6 / 8 – 20 kg/h
Fuel
Gas oil, max. viscosity at 20
°
C: 6 mm
2
/s (1.5
°
E)
Electrical supply
Single phase,
230 V
±
10%
~
50Hz
Motor
Run current 1.5 A – 2750 rpm – 288 rad/s
Capacitor
5
m
F
Ignition transformer
Secondary 8 kV – 16 mA
Pump
Pressure: 7 – 15 bar
Absorbed electrical power
0.33 kW
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pressure regulator, 2
nd
stage
5 – Vacuum gauge connection
6 – Hydraulic jacks with air-damper
7 – Combustion head adjustment screw
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Regulation pressure, 1
st
stage
11 – Economizer
EQUIPMENT
Quantity
Description
2
1
4
1
1
1
1
1
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Hinge
Screw with two nuts for flange
External probe
7 pin plug
4 pin plug
S7351
Fig. 1