Riello 20023353 Installation Instructions Manual Download Page 11

11

 

INSTALLATION

Installation

INSTALLATION

GENERAL INSTRUCTIONS

Assembly

The system must be installed by specialist personnel. Use only 

the assembly material supplied with the solar collector. The sup-

porting framework and all masonry or brickwork fixing points 

must be checked by a person expert in static loading, and must 

be suitable for the nature of the installation site.

Static load

The solar collector must only be installed on roofs or frames 

that are strong enough to support its weight. The strength of 

the roof or frame must be verified on site by a person expert in 

static loading before the solar collector is installed. During this 

process, it is important to verify the suitability of the support-

ing frame to hold the screw fasteners that fix the solar collector 

in place. An expert in static loading must verify that the entire 

frame complies with relevant standards, especially in areas lia-

ble to snow and areas exposed to high winds. Conditions (gusts 

of wind, formation of wind vortices, etc.) at the point where the 

solar collector is to be installed must be carefully considered 

since these can increase the loads on the supporting structure. 

Allow for a maximum permissible total load on each collector of 

850 Pa (possible in the event of a peak wind speed of 130 km/h).

Lightning protection

The metal piping of the solar heating circuit must be connect-

ed to the main potential compensation bar by a (yellow-green) 

copper wire (H07 V-U or R) of at least 16 mm

2

. If a lightning con-

ductor system is already installed, the solar collectors may be 

connected to the existing system. Alternatively, the solar collec-

tor piping may be connected to ground via a ground wire sunk 

into the earth. Ground wires must be sunk outside the house. 

The ground wire must be connected to the potential compensa-

tion bar through a wire of the same diameter.

Water connections

Solar collectors must be connected in series using the threaded 

unions provided. If flexible pipes are not used to connect the 

solar collectors, the piping must be fitted with expansion joints 

(U-type expansion joints, flexible hoses) to absorb thermal ex-

pansion. Provided adequate expansion joints are used, up to 6 

solar collectors may be connected in series. Make sure that the 

unions are located correctly when tightening them. When tight-

ening a union with a pipe wrench or spanner, always hold the 

opposite union steady with a second tool to avoid twisting the 

pipe to which the union is attached.

 

9

All pipes in the water circuit must be insulated in conform-

ity to relevant standards. Lagging and insulation must be 

protected against damage by the weather and birds and 

animals.

Angle of collectors / General

Solar collectors are designed to be installed at angles of be-

tween 15° (minimum) and 75° (maximum). Make sure that the 

bleed and vent valves of the collectors remain open while the 

collectors are being  installed. Take care to protect all fittings, 

connections, bleed and vent valves against dirt and dust etc.. 

In installations which serve primarily to produce domestic hot 

water in the summer, install the collectors facing from east to 

west at an angle of between 20 and 60°. The ideal orientation 

is southwards, at an angle equal to the latitude of the location 

minus 10°. If the system sustains the greatest thermal load in 

the winter (as in systems that combine domestic hot water pro-

duction with central heating), install the collectors facing south 

(or south-east or south-west) at an angle greater than 35°. The 

ideal orientation is southwards, at an angle equal to the latitude 

of the location plus 10°.

Flushing and filling

For safety reasons, the solar collector must be covered, using 

the packaging it came in, for at least two hours before it can be 

filled. In areas liable to frost, fill the collector with an anti-freeze 

heat transfer fluid.

 

9

DO NOT ADD WATER TO THE GLYCOL PREMIX.

 

The anti-freeze supplied for use with solar collectors comes 

ready to use. IT MUST NOT BE MIXED WITH WATER.

 

9

Take care if you flush the system out, because water trapped 

inside the circuit before filling with glycol premix may freeze.

Vent

Bleed the circuit:

 

− On startup (after initial filling) (see the figure on page  12).

 

− Whenever necessary, as in the event of system malfunc-

tioning.

Make quite sure that all air has been bled out of the system.

 

9

Risk of burns from hot fluid inside the collectors.

 

9

Only open the vent valve if the temperature of the fluid in 

the circuit is below 60°C. Make sure that the collectors are 

not hot before you start bleeding the circuit. Always cover 

the solar collectors before bleeding the circuit. Always per-

form bleeding in the morning.

Checking the heat transfer liquid

Check the anti-freeze effect and the pH level of the heat transfer 

liquid every 2 years.

 

− Use an instrument like a refractometer or densimeter to 

check the anti-freeze effect: if the fluid’s density differs 

from that declared in the manufacturer’s technical spec-

ifications, replace the anti-freeze fluid.

 

− Check the pH of the anti-freeze fluid using litmus paper: 

if measured pH differs from that specified in the manu-

facturer’s technical specifications, replace the anti-freeze 

fluid.

 

9

At the end of its useful life, dispose of the product in com-

pliance with applicable legislation.

Summary of Contents for 20023353

Page 1: ...cod 20024195 rev 9 10 2018 CSV 25 35 R EN INSTALLATION INSTRUCTIONS ...

Page 2: ...nts CONTENTS The following symbols are used in this manual 9 9CAUTION Identifies actions that require caution and adequate preparation 0 0STOP Identifies actions that you MUST NOT do This manual Code Rev comprises pages GENERAL INFORMATION 3 1 System layout 3 2 Identification 4 3 Technical specifications 5 4 Connections 7 5 Water circuit 8 INSTALLATION 10 6 Unpacking the product 10 7 Handling 10 8...

Page 3: ...2 H1 L3 Seal Insulation Bottom pipe Glass Vacuum Absorbent coating Collector foot Support frame Direction of flow Evacuated tube Aluminium absorber Top cover plat Top pipe Reflective mirror Description H1 H2 H3 L1 L2 L3 P1 P2 U M CSV 25 R 1730 65 1700 1600 1552 110X14 68 145 mm CSV 35 R 2260 2212 110X20 mm General information ...

Page 4: ...RATURA DI STAGNAZIONE 201 C SUPERFICIE DI APERTURA 2 20 m2 CONTENUTO LIQUIDO 1 6 l SUPERFICIE ASSORBITORE 2 15 m2 PESO A VUOTO 36 5 kg LIQUIDO TERMOVETTORE ACQUA GLICOLE PROPILENICO MAX CONCENTRAZIONE GLICOLE 50 MAX PRESSIONE ESERCIZIO 10 bar da Riello S p A 20038498_E1 EN 12975 Certif 011 7S1766 F 12000025 BAR CODE 128B Anno di produzione CODICE 20038250 RIELLO S p A Via Ing Pilade Riello 7 37045...

Page 5: ...tor a2 0 010 0 011 W m2 K2 Description U M IAM T 50 1 07 IAM L 50 0 954 Efficiency ηcol 64 Tested according to EN 12975 referred to a 33 3 water glycol mix flow rate of 170 l h CSV 25 R 240 l h CSV 25 R and irradiation G 800W m2 Tm Coll _inlet _temp Coll _outlet_temp 2 T m Tm T_ambient G Calculated with a temperature difference of 40K between the solar collector and the surrounding air and with to...

Page 6: ... collector weight kg At angle of 45 At angle of 20 At angle of 45 At angle of 20 CSV 25 R 0 10 low 60 40 100 424 546 10 20 low 80 50 250 595 773 0 10 medium 80 70 100 396 510 10 20 medium 90 80 250 533 691 CSV 35 R 0 10 low 90 80 100 599 771 10 20 low 110 100 250 841 1093 0 10 medium 110 100 100 561 720 10 20 medium 130 120 250 753 976 9 9These specifications are purely indicative The entire struc...

Page 7: ... nut ring nut union olive olive ring nut union olive olive ring nut stub pipe stub pipe stub pipe Collectors in the same line must be connected so that the heat transfer fluid flows through them in series Lines of solar collectors can be connected either in series provided each line contains no more than 6 collectors or in parallel The complete circuit must always be hydraulically balanced See the...

Page 8: ...16 Manual bleed valve accessory 17 Storage cylinder bottom temperature sensor 18 Storage cylinder top temperature sensor 19 Heat transfer fluid recovery M Collector outlet R Collector return 9 9Connect no more than 6 collectors in series 9 9We recommend the use of stainless steel pipes specially made for solar collectors for the outlet return and probe pipes The probe cable should be of the shield...

Page 9: ...0 500 400 300 200 100 0 0 1000 2000 3000 4000 5000 6000 FLOW RATE l h _______ CSV 25 R _ _ _ _ CSV 35 R Diameter of connection pipes for a specific flow rate of 30 lt m2 h Total surface area m2 2 4 6 12 14 20 Diameter of copper pipe mm 10 12 14 18 Diameter of steel pipe inch 3 8 1 2 1 2 3 4 ...

Page 10: ...an integral part of the solar con nector Once located read it thoroughly and keep it safe A B Handling Once you have removed the outer packaging proceed as follows to unpack and handle the solar collector Remove the PVC wrapping to free the solar collector from the pallet Tilt the solar collector slightly and grip it at the four points shown A to lift it Use a hoist or other suitable lifting equip...

Page 11: ...d in conform ity to relevant standards Lagging and insulation must be protected against damage by the weather and birds and animals Angle of collectors General Solar collectors are designed to be installed at angles of be tween 15 minimum and 75 maximum Make sure that the bleed and vent valves of the collectors remain open while the collectors are being installed Take care to protect all fittings ...

Page 12: ... be cause the liquid becomes darker 9 FILLING THE CIRCUIT 2 FILLING 1 Open the non return valve A 2 Open the air vent at the highest point in the system see figure alongside and keep it open throughout the filling operation 3 Open the vent valve 7 4 Pump the heat transfer fluid around the circuit with an external filling pump until all air bubbles have been elimi nated Close the manual bleed valve...

Page 13: ...required if this pump is used Checks On completion of the installation perform the checks listed in the table below 10 CHECKS Collector circuit Cold circuit pressure ____bar see table above Collector circuit seal test Safety valve check Anti freeze checked to ___ C pH of heat transfer fluid ____ Collector circuit bled Flow rate of 30 l h per m2 checked Non return valve functioning Solar collectors...

Page 14: ...e tube 3 downwards twisting it gently to release it from the top seal Remove the tube from the bottom of the collector If you do not have sufficient room to remove the tube down wards proceed as follows Remove the tube from the collector foot as instructed above Pull the tube down about 20 cm Hold the tube in a glove lift it gently and swivel it to the left or right This bends the copper pipes ins...

Page 15: ... fault e g a large dent is found they can be replaced quickly and easily Proceed as follows taking all the necessary precautions to re move a damaged reflector Unscrew and remove the plug 1 from the foot of the col lector Remove the bracket 2 into which the plug was screwed by bending back the clips 3 Remove the reflector 4 without moving its glass tube 1 4 2 3 4 ...

Page 16: ...llo 7 37045 Legnago VR www riello com The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore liable to modification without notice ...

Reviews: