Start-up, calibration and operation of the burner
6.1
Notes on safety for the first start-up
6.2
Adjustments prior to ignition
Combustion head adjustment has already been already de-
scribed in the section “Combustion head adjustment” on pag. 26.
In addition, the following adjustments must also be made:
Open manual valves upstream from the gas train.
Adjust the minimum gas pressure switch to the start of the
scale.
Adjust the maximum gas pressure switch to the end of the
scale.
Adjust the air pressure switch to the start of the scale.
Adjust the pressure switch for the leak detection control
(PVP kit)(Fig. 36 on pag. 41) according to the instructions
supplied with the kit.
Purge the air from the gas line.
We recommend using a plastic tube routed outside the build-
ing and to purge air until gas is smelt.
Fit a U-type pressure gauge or a differential pressure gauge
(Fig. 27), with socket (+) on the gas pressure of the pipe
coupling and (-) in the combustion chamber.
The manometer readings are used to calculate MAX burner
output using the Tab. N.
Connect two lamps or testers to the two gas line solenoids to
check the exact moment in which voltage is supplied. This
operation is unnecessary if each of the two solenoids is
equipped with a pilot light that signals voltage passing
through.
6
Start-up, calibration and operation of the burner
WARNING
The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
tions of the laws in force.
WARNING
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
Before igniting the burner, see the paragraph
vedi “Safety test - with gas feeding closed” a
pag. 39.
CAUTION
Before starting up the burner, it is good practice to
adjust the gas train so that ignition takes place in
conditions of maximum safety, i.e. with gas deliv-
ery at the minimum.
Fig. 27
20069491
Summary of Contents for 1135T1
Page 2: ...Translation of the original instructions...
Page 29: ...27 20173117 GB Installation Fig 20 No Setpoint air gas Max burner output kW 20081480...
Page 53: ...51 20169327 GB Appendix Electrical panel layout ALL MODELS RS 310 RS 410 DIRECT START UP...
Page 54: ...20169327 52 GB Appendix Electrical panel layout RS 310 RS 610 STAR TRIANGLE START UP...
Page 57: ...55 20169327 GB Appendix Electrical panel layout ALL MODELS...
Page 58: ...20169327 56 GB Appendix Electrical panel layout ALL MODELS...
Page 59: ...57 20169327 GB Appendix Electrical panel layout 0 ALL MODELS...
Page 61: ...59 20169327 GB Appendix Electrical panel layout 0 1 1 1 2 ALL MODELS...