33
UPS
CONFIGURATION
The table below illustrates all the possible configurations available to the user in order to best adapt the UPS to individual
requirements. It is possible to perform these operations by using the LCD configuration and ViewPower software.
FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
Output voltage*
Selects the nominal output
voltage
208V
208/220/230/240
Converter mode*
Converter mode enable or
disable
Disabled
•
Enabled
•
Disabled
Output frequency
Selects the nominal output
frequency when converter
mode enable
50Hz
•
50 Hz
•
60 Hz
ECO mode
ECO mode enable or
disable
Disabled
•
Enabled
•
Disabled
Bypass when
UPS is off
Bypass when UPS is off
enable or disable
Enable
•
Enabled
•
Disabled
Autonomy limit
Maximum battery operation
time
Disabled
•
Disabled (complete battery discharge)
•
(1 - 999) minutes. in 1 minutes steps
Battery AH
Battery AH(1PCS )
7 or 9
7
– 999 in AH steps
Charger current
Select Charger current
1Amp
•
1-4Amp
Charger current
Calibration
Calibration Charger current
0
•
± 0~± 5
* If converter mode is enabled or 208V output is selected, the UPS output power will be de-rate.