26
D
ISPLAY PANEL MESSAGES
This chapter describes, in detail, the various information that can be displayed on the LCD.
UPS
STATUS MESSAGES
ICON
STATUS
DESCRIPTION
Fixed
Indicates a fault
Flashing
Indicates a warning /The UPS is in stand-by mode
Fixed
Indicates regular operation
Fixed
The UPS is operating from the mains
Flashing
The UPS is operating from the mains, but the output voltage is not
synchronised with the mains voltage or the UPS is turning on.
Fixed
The UPS is operating from the battery. In this condition, the UPS emits an
acoustic signal (beep) at regular 4-second intervals.
Flashing
Low battery pre-alarm. Indicates that battery autonomy is coming to an
end. In this condition, the UPS will sound every 2 seconds.
Fixed
Indicates that the loads connected to the UPS are powered by the bypass
Dynamic
Indicates the estimated percentage charge of the batteries
Dynamic
Indicates the percentage of load connected to the UPS compared with the
nominal value.
Flashing
Maintenance is required. Contact the support centre.
Fixed
Indicates that the timer is active (programmed switch-on and switch-off).
The timer can be activated/deactivated using the software provided.
Fixed
Power output on Energy Share socket.