8
TECHNICAL DATA
(1)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2)
Pressure at pressure switch test point 20)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer»s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional)
•
OUTPUT POWER REGULATOR KIT:
Under modulating operation, the burner automatically adapts to one of an infinite number of firing
rates between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two compo-
nents should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
•
GAS TRAIN ACCORDING TO REGULATION EN 676
:
see page 22.
Note.
The installer is responsible for the addition of any safety device not forseen in the present manual.
MODEL
RS 300/E BLU
RS 400/E BLU
TYP
849 T1
850 T1
OUTPUT
(1)
max.
kW
1350 … 3800
1800 … 4500
min.
kW
500
800
FUEL
NATURAL GAS: G20 (methane) - G21 - G22 - G23 - G25
Gas pressure at maximum delivery.
(2)
Gas: G20/G25
mbar
18 / 26
33.4 / 38.7
OPERATION
Continuous / Intermittent
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral ~ +/-10%
50 - three-phaes
FAN MOTOR
(star-delta starting)
rpm
V
kW
A
2900
230/400
4,5
15,8 - 9,1
2900
230/400
7,5
23 - 16
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
kW max
6
9
ELECTRICAL PROTECTION
IP 54
CONFORMITY TO EEC DIRECTIVES
98/37 - 90/396 - 89/336 - 73/23
NOISE LEVELS
(3)
dBA
82
85
APPROVAL
class 3 (EN 676)
CE
0085 BO 0341
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+ 500°C
PT 100
3010110
RWF40 BASIC
RWF40 HIGH
3010356
3010357
Pressure
0...2,5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
•
KIT AZL (display and operating unit)
Code
3010355
•
INFRARED SENSOR KIT QRI
Code
3010354
•
PRESSURE SWITCH KIT (for leak detection control)
Code
3010344
Summary of Contents for RS 300/E BLU
Page 36: ...37 RS 300 E BLU ...
Page 37: ...38 RS 400 E BLU ...
Page 38: ...39 ...
Page 39: ...40 RS 300 E BLU ...
Page 40: ...41 RS 400 E BLU ...
Page 41: ...42 ...
Page 42: ...43 ...
Page 43: ...44 ...
Page 44: ...45 ...
Page 45: ...46 ...
Page 46: ...47 ...
Page 47: ...48 ...
Page 48: ...49 ...
Page 49: ...50 ...
Page 50: ...51 ...