2431
1
GB
Forced draught gas burner
GS20
CODE
3755613
TYPE
556T1
TECHNICAL FEATURES
For gas family 3 (LPG) ask for separate kit.
◆
The burner meets protection level of IP 40, EN 60529.
◆
CE marking according to Gas Appliance Directive 90/396/EEC; PIN 0063AP6680.
◆
According to directives: EMC 89/336/EEC, Low Voltage 73/23/EEC, Machines 98/37/EEC and
Efficiency 92/42/EEC.
◆
Gas train according to EN 676.
NOTE
The grommet (5) and the screw for fixing the cover (6) supplied with the burner, must be fitted to
the same side of the gas train.
Thermal output
81 – 232 kW
–
70,000 – 200,000 kcal/h
Gas
(Family 2)
Net heat value
8 – 12 kWh/m
3
–
7,000 – 10,340 kcal/m
3
Pressure
min. 20 mbar
–
max. 35 mbar
Electrical supply
single phase,
230 V
±
10%
~
50Hz
Motor
230 V / 1.4 A
Capacitor
5
µ
F
Ignition transformer
primary 230 V / 1.8 A – secondary 8 kV / 30 mA
Absorbed electrical power
0.25 kW
COUNTRY
DE
DK - AT - GR - SE
GB - IE
LU
GAS CATEGORY
II2ELL3B/P
II2H3B/P
II2H3P
II2E3B/P
1 – Air-dampers
2 – Screws for fixing the air-damper
3 – 7 pole socket for electrical supply
and control
4 – 6 pole socket for gas train
5 – Grommet
6 – Screw for fixing the cover
7 – Lock-out lamp and reset button
2
5
1
6
7
D5147
Fig. 1
3
2
4