8
TECHNICAL DATA
(1)
Reference conditions: Ambient temperature 20°C - Barometric pressure 1000 mbar - Altitude 100 m a.s.l.
(2)
Pressure at pressure switch test point 20)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(3)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional)
MODEL
RL 300/B MZ
RL 400/B MZ
TYP
966 T
967 T
OUTPUT
(1)
DELIVERY
(1)
2nd stage
(min - max)
kW
kg/h
1250 ÷ 3550
105 ÷ 301
2000 ÷ 4450
169 ÷ 378
1st stage
(min)
kW
kg/h
600
50
1000
84
FUEL
LIGHT OIL
- net calorific value
kWh/kg
Mcal/kg
11.8
10.2 (10.200 kcal/kg)
- density
kg/dm
3
0.82 - 0.85
- viscosity at 20 °C
mm
2
/s
max 6 (1.5 °E - 6 cSt)
OPERATION
- Intermittent (min. 1 stop in 24 hours)
- Two-stage (high and low flame) and single-stage (all - nothing)
NOZZLES
number
2
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
3N ~ 400 / 230V +/-10% 50 Hz
ELECTRIC MOTORS
rpm
2800
2800
FAN MOTOR
(star-delta starting for RL 400)
V
kW
A
230/400
4,5
15,8 - 9,1
230/400
7,5
23 - 16
PUMP MOTOR
V
kW
A
230/400
1,1
3
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 2 x 5 kV
1,9 A - 35 mA
PUMP
delivery at 20 bar (kg/h)
pressure range (bar)
fuel temperatur (°C)
380
7 - 40
140
ELECTRICAL POWER CONSUMPTION
kW max
6
9
ELECTRICAL PROTECTION
IP 54
CONFORMITY TO EEC DIRECTIVES
90/396 - 89/336 - 73/23
NOISE LEVELS
(3)
dBA
83
85
APPROVAL
class 2 (EN 267)
CE
APPROVAL
DIN
•
DIAGNOSTICS INTERFACE KIT
Code
3002719
•
SILENCER BOX KIT
Code
3010376