background image

8 — English

CONTROL PANEL CORD (NOT PROVIDED)

See Figure 1.

The 25-ft. control panel cord (Model RDEC25) has a 240 Volt, 
20 Amp twist lock plug on one end and a 240 Volt, 20 Amp 
twist lock receptacle on the other end. It also has a 12 Volt 
DC engine control connector on each end. When using this 
cord, the removable control panel can provide power through 
the 2 x 120 Volt duplex GFCI outlets on the control box.

NOTICE:

Use removable control panel only with RDEC25 
control panel cord (not provided). Do not exceed 
separation length of 75 ft. or a combination of three 
RDEC25 control panel cords. 

NOTICE:

Operating voltage and frequency requirement of 
all electronic equipment should be checked prior 
to plugging them into this generator. Damage may 
result if the equipment is not designed to operate 
within a +/- 10% voltage variation, and +/- 3 hz 
frequency variation from the generator name 
plate ratings. To avoid damage, always have an 
additional load plugged into the generator if solid 
state equipment (such as a television set) is used. 
A power line conditioner is recommended for some 
solid state applications.

ELECTRICAL

GROUND FAULT CIRCUIT INTERRUPTER

See Figure 2.

The 20 amp, 120 volt receptacles on the generator are pro-
tected by a Ground Fault Circuit Interrupter (GFCI), which 
guards against the hazards of ground fault currents. An 
example of ground fault current is the current that would 
flow through a person who is using an appliance with faulty 
insulation and, at the same time, is in contact with an electri-
cal ground such as a plumbing fixture, wet floor, or earth.
GFCI receptacles do not protect against short circuits, 
overloads, or shocks.
The GFCI receptacles can be tested with the TEST and 
RESET buttons.

To test:

 

Depress the TEST button. This should cause the Reset 
button to pop out.

  To restore power, depress the RESET button.

Perform this test monthly to ensure proper operation of the 
GFCI. If the generator is stored outdoors, unprotected from 
the weather, test the GFCI receptacle before each use.

GENERATOR CAPACITY

Make sure the generator can supply enough continuous (run-
ning) and surge (starting) watts for the items you will power 
at the same time. Follow these simple steps.
1.  Select the items you will power at the same time.
2.  Total the continuous (running) watts of these items. This is 

the amount of power the generator must produce to keep 
the items running. See the wattage reference chart at right.

3.  Estimate how many surge (starting) watts you will need. 

Surge wattage is the short burst of power needed to 
start electric motor-driven tools or appliances such as a 
circular saw or refrigerator. Because not all motors start 
at the same time, total surge watts can be estimated by 
adding only the item(s) with the highest additional surge 
watts to the total rated watts from step 2.

ELECTRIC MOTOR LOADS

It is characteristic of common electric motors in normal operation to draw up to six times their running current while starting. 
This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails to start or 
reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the requirements 
of the tool or appliance being used compared to the rated output of the generator.

Motor Size (H.P.)

Running Watts

Watts Required to Start Motor

Universal

Capacitor

Split Phase

1/8

 275

 N/A

 850

1200

1/6

 275

 600

 850

2050

1/4

 400

 800

1050

2400

1/3

 450

 950

1350

2700

1/2

 600

1000

1800

3600

3/4

 850

1200

2600

1

1100

N/A

3300

Summary of Contents for RD906812A

Page 1: ...d de uso y seguri dad para el operador Con el debido cuidado le brindar muchos a os de s lido funcionamiento y sin problemas ADVERTENCIA Para reducir el riesgo de lesiones el usuario debe leer y compr...

Page 2: ...eferenced in the operator s manual Consulter l encart volets afin d examiner toutes les figures mentionn es dans le manuel d utilisation Consulte esta secci n desplegable para ver todas las figuras a...

Page 3: ...dle poign e mango L Fuel tank r servoir de carburant tanque de combustible M Fuel tank vapor vent vent de vapeur du r servoir de carburant respirador del vapor del tanque de combustible N Ground termi...

Page 4: ...Axle essieu eje 2 Wheel roue rueda 3 Washer rondelle arandela 4 Hitch pin axe de blocage pasador del enganche 5 Screw 2 in vis 2 po tornillo 2 pulg 6 Washer rondelle arandela 7 Leg with rubber foot p...

Page 5: ...art A Oil cap dipstick bouchon jauge d huile tapa de relleno de aceite varilla medidora de aceite B Oil fill hole orifice de remplissage d huile agujero de llenado de aceite A Fig 14 Fig 15 A Fuel cap...

Page 6: ...inet de carburant v lvula de combustible B Off arret apagado C On marche encendido D Choke lever levier de volet de d part palanca del anegador E Start position position de d marrage posici n de arran...

Page 7: ...n de drenaje del aceite A B C A Fuel line conduite de carburant conducto de combustible B Petcock robinet de carburant llave de purga C Fuel valve robinet de carburant v lvula de combustible C A B Fi...

Page 8: ...this generator must be properly grounded by use of a third wire or be Double Insulated It is recommended to 1 Use electrical devices with 3 prong grounded plugs 2 Use an extension cord intended for o...

Page 9: ...r operate the engine in a confined space building near open windows or in other unventilated space where dangerous carbon monoxide fumes can collect Carbon monoxide a colorless odorless and extremely...

Page 10: ...This means the system ground is connected electrically to the AC neutral wire Do not allow the generator s gas tank to overflow when filling Fill to 1 in below the top neck of the gasoline tank to all...

Page 11: ...rd To reduce the risk of serious injury avoid attempting to lift the generator alone Ground Consult with local electrician to determine grounding requirements before operation Electrocution Failure to...

Page 12: ...abiertas S lo util celo AL AIRE LIBRE y lejos de ventanas puertas y respiraderos Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxide This is a poison you cann...

Page 13: ...he exhaust Risk of Fire Check for any fuel overflow or leaking Stop the engine before refueling DANGER DANGER PELIGRO Risque d incendie V rifier l absence de d bordement ou de fuite de carburant Arr t...

Page 14: ...tacles can be tested with the TEST and RESET buttons To test Depress the TEST button This should cause the Reset button to pop out To restore power depress the RESET button Perform this test monthly t...

Page 15: ...the first load preferably the largest load you have 3 Permit the generator output to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again p...

Page 16: ...ge and load and alerts the operator when periodic engine maintenance is needed NOTE GenSmart load indicator monitors the load only for the 120 Volt 20 Amp GFCI outlets on the removable control panel I...

Page 17: ...operated the product If any parts are damaged or missing please call 1 866 539 1710 for assistance WARNING If any parts are damaged or missing do not operate this product until the parts are replaced...

Page 18: ...first then connect the black wire to the negative terminal using the bolts nuts and washers provided Make sure all connections are tight NOTE Be careful not to short across the terminals when installi...

Page 19: ...nt to inflict serious injury WARNING Do not use any attachments or accessories not recommended by the manufacturer of this product The use of attachments or accessories not recommended can result in s...

Page 20: ...her than adding fuel stabilizer directly into the generator s fuel tank Replace and secure the fuel tank cap Start and run the engine for at least 5 minutes to allow stabilizer to treat the entire fue...

Page 21: ...enance Warning System At every 100 hours of use the GenSmart monitoring sys tem will display a flashing message informing the operator to service the engine as required by the engine operator s manual...

Page 22: ...TE Do not allow the grip to snap back after starting return it gently to its original place Allow the engine to run for 15 30 seconds then move the choke lever left to the RUN position Place the idle...

Page 23: ...completely WARNING Do not change engine lubricant while it is hot Accidental contact with hot engine lubricant could result in serious burns Reinstall the oil drain plug and tighten securely Refill wi...

Page 24: ...to drain completely into container Retighten drain screw NOTE Consulthazardouswastemanagementguidelinesin your area for the proper way to dispose of used fuel MAINTENANCE REPLACING FUEL FILTER See Fi...

Page 25: ...rt circuit may result Keep away from children Failure to comply with these warnings could result in fire and or serious injury MAINTENANCE STORAGE When preparing the generator for storage allow the un...

Page 26: ...Filter Change Air Filter Check Adjust Spark Plug Replace Spark Plug Check Adjust Idle Speed Check Adjust Valve Clear ance Clean Fuel Tank and Filter Check Fuel Hose Fuel Filter Inspect Replace Check A...

Page 27: ...control switch is ON and load is less than 300 watts Check air filter element Clean or replace as needed Drain fuel and carburetor Refuel with fresh gasoline If problem continues contact your nearest...

Page 28: ...World Technologies Inc disclaim any and all express or implied warranties with respect to the gasoline engine One World Technologies Inc P O Box 35 Highway 8 Pickens SC 29671 RIDGID GENERATOR 3 YEAR...

Page 29: ...be warranted for the warranty period defined in subsection b 2 If any such part fails during the period of warranty coverage it must be repaired or replaced by the manufacturer issuing ONE WORLD TECHN...

Page 30: ...Emission Control System Warranty Yamaha Motor Corporation USA also warrants to the ulti mate purchaser of each engine covered by this warranty that the product is designed built and equipped so as to...

Page 31: ...lation EGR System EGR valve body and carburetor spacer if applicable EGR rate feedback and control system 5 Air Injection System Air pump or pulse valve Valves affecting distribution of flow Distribut...

Reviews: