background image

8 — English

NOTICE:

Operating voltage and frequency requirement of 
all electronic equipment should be checked prior 
to plugging them into this generator. Damage may 
result if the equipment is not designed to operate 
within a +/- 10% voltage variation, and +/- 3 hz 
frequency variation from the generator name 
plate ratings. To avoid damage, always have an 
additional load plugged into the generator if solid 
state equipment (such as a television set) is used. 
A power line conditioner is recommended for some 
solid state applications.

GROUND FAULT CIRCUIT INTERRUPTER

See Figure 1.

The 20 amp, 120 volt receptacles on the generator are pro-
tected by a Ground Fault Circuit Interrupter (GFCI), which 
guards against the hazards of ground fault currents. An 
example of ground fault current is the current that would 
flow through a person who is using an appliance with faulty 
insulation and, at the same time, is in contact with an electri-
cal ground such as a plumbing fixture, wet floor, or earth.
GFCI receptacles do not protect against short circuits, 
overloads, or shocks.
The GFCI receptacles can be tested with the TEST and 
RESET buttons.

To test:

 

Depress the TEST button. This should cause the Reset 
button to pop out.

  To restore power, depress the RESET button.

Perform this test monthly to ensure proper operation of the 
GFCI. If the generator is stored outdoors, unprotected from 
the weather, test the GFCI receptacle before each use.

ELECTRICAL

GENERATOR CAPACITY

Make sure the generator can supply enough continuous (run-
ning) and surge (starting) watts for the items you will power 
at the same time. Follow these simple steps.
1.  Select the items you will power at the same time.
2.  Total the continuous (running) watts of these items. This is 

the amount of power the generator must produce to keep 
the items running. See the wattage reference chart at right.

3.  Estimate how many surge (starting) watts you will need. 

Surge wattage is the short burst of power needed to 
start electric motor-driven tools or appliances such as a 
circular saw or refrigerator. Because not all motors start 
at the same time, total surge watts can be estimated by 
adding only the item(s) with the highest additional surge 
watts to the total rated watts from step 2.

Example:

Tool or Appliance

Running  

Watts*

Additional  

Starting Watts*

Quartz Work Light 
(1000 Watt)

1000

0

Drill (1/2 inch,  
5.4 amps)

600

900

Airless Sprayer (1/3 
HP)

600

1200

Radio

200

0

Fan

60

200

2460 Total

Running Watts

1200 Highest 

Starting Watts

 

Total Running Watts 

2460

 

Highest Starting Watts  + 1200

 

Total Starting Watts Needed 

  3660

ELECTRIC MOTOR LOADS

It is characteristic of common electric motors in normal operation to draw up to six times their running current while starting. 
This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails to start or 
reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the requirements 
of the tool or appliance being used compared to the rated output of the generator.

Motor Size (H.P.)

Running Watts

Watts Required to Start Motor

Universal

Capacitor

Split Phase

1/8

 275

 N/A

 850

1200

1/6

 275

 600

 850

2050

1/4

 400

 800

1050

2400

1/3

 450

 950

1350

2700

1/2

 600

1000

1800

3600

3/4

 850

1200

2600

1

1100

N/A

3300

Summary of Contents for RD903612 Series

Page 1: ...d de uso y seguridad para el operador Con el debido cuidado le brindar muchos a os de s lido funcionamiento y sin problemas ADVERTENCIA Para reducir el riesgo de lesiones el usuario debe leer y compre...

Page 2: ...eferenced in the operator s manual Consulter l encart volets afin d examiner toutes les figures mentionn es dans le manuel d utilisation Consulte esta secci n desplegable para ver todas las figuras a...

Page 3: ...20 amp receptacles GFCI protected prises 120 V C A 20 A prot g par un disjoncteur de fuite la terre 120 V de CA 20 A recept culos protegido por GFCI K 120 V AC 30 amp receptacle prise 120 V C A 30 A...

Page 4: ...le release knob goupille de d gagement de la poign e conjunto de pasador de afloje de mango Fig 7 HRS Hz W SMART DISPLAY 1 Axle bolt boulon de l essieu perno de eje 2 Wheel roue rueda 3 Washer rondell...

Page 5: ...de CA GFCI 20 A recept culos Fig 10 Fig 13 Fig 12 Fig 11 C 120 volt AC 20 amp receptacles GFCI protected prises 120 V C A 20 A prot g par un disjoncteur de fuite la terre 120 V de CA 20 A recept culo...

Page 6: ...A B A Fig 15 A Fuel valve on robinet de carburant marche v lvula de combustible encendido B Fuel valve off robinet de carburant arret v lvula de combustible C Engine switch OFF commutateur de moteur...

Page 7: ...1 A Fuel line conduites de carburant conducto de combustible B Fuel filter filtre carburant filtro de combustible A Fuel line conduite de carburant conducto de combustible B Petcock robinet de carbura...

Page 8: ...m this generator must be properly grounded by use of a third wire or be Double Insulated It is recommended to 1 Use electrical devices with 3 prong grounded plugs 2 Use an extension cord intended for...

Page 9: ...start or run the engine inside a closed or partially enclosed area Breathing exhaust fumes will kill you Do not start or operate the engine in a confined space building near open windows or in other...

Page 10: ...cause burn injury This generator has a neutral bonded condition This means the system ground is connected electrically to the AC neutral wire Do not allow the generator s gas tank to overflow when fil...

Page 11: ...vere burns or death Hot Surface To reduce the risk of injury or damage avoid contact with any hot surface Lifting Hazard To reduce the risk of serious injury avoid attempting to lift the generator alo...

Page 12: ...is is a poison you cannot see or smell NEVER use inside a home or garage EVEN IF doors and windows are open Only use OUTSIDE and far away from windows doors and vents HOTSURFACEWARNING Do not touch th...

Page 13: ...puede producir chispas propensas a iniciar incendios cerca de vegetaci n seca Es posible que se necesite un parachis pas El operador debe ponerse en contacto con las agencias contra incendios locales...

Page 14: ...s for the items you will power at the same time Follow these simple steps 1 Select the items you will power at the same time 2 Total the continuous running watts of these items This is the amount of p...

Page 15: ...permit the generator to stabilize 6 Repeat steps 4 and 5 for each additional load Never add more loads than the generator capacity Take special care to consider surge loads in generator capacity as pr...

Page 16: ...with the recoil starter grip to start the engine It is also used to turn the engine off FUEL TANK The fuel tank has a capacity of 4 gallons FUEL VALVE Fuel flow from the fuel tank to the engine is tur...

Page 17: ...product Any such alteration or modification is misuse and could result in a hazardous condition leading to possible serious personal injury WARNING Do not attempt to operate the generator until assem...

Page 18: ...O alarm in the home If you start to feel sick dizzy or weak after the generator has been running move to fresh air RIGHT AWAY See a doctor You could have carbon monoxide poisoning DANGER Failure to pr...

Page 19: ...her approved fuel container and shaking gently to combine NOTE Tocontroltheamountoffuelstabilizerbeingadded to the engine always mix fuel stabilizer with gasoline before fueling the tank rather than a...

Page 20: ...On a level surface with the engine off check the lubricant level before each use of the generator OPERATION NOTE If location of generator is not level the unit may not start or may shut down during o...

Reviews: