3. Control mode:
• After limits are detected, the controller will enter control mode.
Room temperature is displayed.
•The letters “Cr” indicate the Remote Wall Thermostat temperature as
a Source for temperature display. When “CO” is displayed the Source
for temperature display is the Onboard controller & sensor. “CE” is
displayed to indicate Control Temperature Error i.e. Wall stat temper-
ature is displayed, but no temperature is selected for control purpos-
es.
• The controller will now drive the diffuser in the direction to control
room conditions.
• In
PICTURE 1
the display indicates that cooling mode is required to
get room conditions under control and the diffuser is busy driving
open.
• In this mode Room temperature is displayed. If Room temperature
was colder than set-point, heating mode would have been required
to get room conditions under control.
•
PICTURE 2
indicates the diffuser has reached the fully open posi-
tion.
•
PICTURE 3
indicates the diffuser is in heating mode and has
reached the minimum stop position for heating. The neck heater is
on as displayed. The diffuser could also be in heating mode without
the neck heater activated. The heater (if fitted) will only be activated
when the control disc reaches the correct position for heating.
(Factory set at 30% flow)
4) Set-point adjustment:
• To adjust the set-point, either the “UP” or “DOWN” buttons must
be pressed.
• After one of these buttons have been pressed, the current set-point
will be displayed.
• While in this screen, press either the “UP” or “DOWN” button to
adjust the set-point value.
The value displayed will now flash.
• Press the “ENTER/ACCEPT” button to be automatically accepted or
wait for the new setpoint.
• The 2 top left digits will indicate the Source of the set-point and
which set-point is Active respectively. If the display shows “r1”, this
indicates the Wall thermostat set-point is the source and setpoint 1,
ie “normal control” is active. Should the digits show “o2” then the
setpoint is active on the onboard controller and the back-off set-
point is active.
PICTURE 2
PICTURE 1
COOLING MODE
INDICATOR
HEATING MODE
INDICATOR
RE-HEATING MODE
INDICATOR
PICTURE 3