5

higher than 50%), recharging should not be deferred for a long time.   

z

 

Low and permanent overcharge is another cause of premature wear. The Invertek 
Charger delivers the current necessary for battery charge and adapts itself to supply 
the optimum end of charge.   

z

 

The accidental and violent overcharge or higher end of charge current produces early 
destruction by excessive rise of temperature. The temperature should not exceed 50°C. 
By the regulation of the current, the Invertek protects the battery from the temperature 
rise at the end of charge.   

It is advisable to   

z

 

Put batteries in a well ventilated area 

z

 

Not to smoke near batteries 

z

 

Take the battery manufacturer prescriptions into consideration 

 

Accidental Leakage Current between Line And Earth   

z

 

Connections will be realized by an electrician or a professional installer. 

z

 

The charger must be connected to a system having a two-pole differential circuit 
breaker with 30 mA sensitivity. 
 

Accidental Leakage Current between Charge Circuit and Earth   

z

 

To detect accidental leakage currents to earth, you must use a safety device outside 
the charger. 

z

 

The rating and nature of the protection must be ensured by the installer. 

z

 

Special precautions are recommended on any installation where there is a danger of 
electrolytic effects. 

z

 

Regulations require the presence of a battery cut-out on the pole and on 
the output – pole. 
 

Precautions Regarding Lightning Strike 

In geographic zones exposed to a high risk of lightning strikes, it may be recommended 
fitting a lightning conductor on the inlet side of the charger. 

Rich Electric will not take 

charge of

 

damaged caused by lightning strike. 

 

Precautions Regarding Electromagnetic Interference 

z

 

Make sure the length of the cables and screening connections are kept as short as 
possible. 

z

 

Separate the power supply cables from output cables. 

z

 

Cables must only carry the charger power supply. Branch or bridging connections in 
order to supply another equipment are too be banned.   

 
Installation 

The location of the Invertek charger must be chosen by the following criteria:   
Protection from unauthorized handling.   
Dry dust free room, no condensation, no rodents. 
Keep ventilation holes free. The ventilation of the Invertek is designed in such a way that 
it will work most efficiently when mounted horizontally.   
Before any connection, put the switch on the right charging curve. 

Summary of Contents for INVERTEK ADC-15U-242A

Page 1: ...INVERTEK SWITCH MODE BATTERY CHARGER MICROPROCESSOR SYSTEM USER MANUAL FOR ALL PATTERNS 1 AND 3 OUTPUTS RICH ELECTRIC CO LTD...

Page 2: ...dvanced Charging Technique 3 Safety Devices 3 Options 4 Safety Instruction 4 Installation 5 Front Panel 7 LED Indicators 7 Instruction of Charging Curve Selection 7 DC Power Supply 9 BTS Remote Contro...

Page 3: ...e market to allow the battery to be connected and used constantly while still offering a real BOOST high voltage charge over short period The charger switches back to top up mode automatically In acco...

Page 4: ...f energy in the least possible time FLOATING Top Up Charge The charger supplies just the current necessary to keep the battery at a constant and stable voltage floating voltage This charging mode allo...

Page 5: ...the batteries 2 Extract fixing screw from wires cover and remove it 3 Connect the sensor connector to the green terminal on the PCB See figure A 4 Connect charger to the mains 5 Fix the temperature se...

Page 6: ...utside the charger z The rating and nature of the protection must be ensured by the installer z Special precautions are recommended on any installation where there is a danger of electrolytic effects...

Page 7: ...use car 1 x 15A 2 x 15A 2 x 30A WARNING Check carefully the tightness of the battery connections to the charger risk if not properly tightened Rich Electric will not take charge of damage caused by a...

Page 8: ...e charger disconnect the mains wait few minutes and reconnect the charger on mains Over Voltage Battery overcharge Ubat 16V for 12V system and 32V for 24V system If Ubat 16V for 12V system and 32V for...

Page 9: ...andard lead acid unsealed 14 4V 13 5V 30 3 14 2V 13 8V 100 4 14 2V 13 8V 70 5 Sealed lead acid Gel Cell 14 2V 13 8V 30 6 14 6V 14 0V 100 7 14 6V 14 0V 70 8 Lead calcium Standard charge 14 6V 14 0V 30...

Page 10: ...ST VOLTAGE to set the first two digits of desired voltage Refer to the below table for what 0 F represents Rotate Switch Boost Volt Rotate Switch Boost Volt Rotate Switch Boost Volt Rotate Switch Boos...

Page 11: ...he battery or check the level of water Battery is quickly empty Sulfate on stagnation Charge discharge several time the battery or check the charging curve or replace the battery Consumption on the ba...

Page 12: ...ng Capacity 20A 40A 60A Frequency 50Hz 60Hz Output Patterns 1 or 3 Input Voltage U bat 2 Output Current I bat 10 Charging Curve Type 3 states IUU type Boost Charge Absorption Charge Floating Charge Ch...

Page 13: ...cid Gel Cell Lead calcium standard charge deep discharge User define Working Temperature 10 45 Storage Temperature 20 70 Protection Feature Against output short circuit battery discharge in the event...

Reviews: