1second pause.
If DIP17 ON and DIP6 ON
If the gate is opening and a vehicle crosses the photo beam, the gate will
continue to open. When the vehicle leaves, the gate will stop and then
closes automatically after 1second pause.
If the complete gate open position is reached before the vehicle leaving, the
DIP17 will be ignored and the automatic closing will be managed in according
to the DIP3 position.
PAY ATTENTION: it is highly recommended to check photocells operation
at least every 6 months.
SAFETY ENCODER (PLUS operators, only)
The Encoder acts as a safety device both during gate closing and opening by
reversing the motor movement in case of impact detection. Any impact is
detected if the motor shaft turning has been suddenly and unexpected blocked.
If the Encoder is faulty (lack of power, disconnected cables, broken or defective
disk), the gate will not move.
STATE OF ALARM FROM ENCODER impact detection
If the gate is moving and the first encoder impact detection occurs, the gate will
reverse in the opposite direction. If a further encoder impact detection occurs,
the gate will reverse again just for 1second. Then, it will stop and the alarm
status will be indicated by the blinking unit (flashes for 1minute) and by led DL1
(blinks every 2 seconds).
To recover the normal gate operation, it is necessary towait 1 minute or press
any control buttons.
SAFETY STRIP (EDGE - COM)
If an obstacle presses the safety strip:
- while the gate is still, it will not move neither in opening nor in closing
- while the gate is closing, the gate will open
- while the gate is opening, the gate will close
In case the safety strip is held pressed a further quick reversion, after 2seconds,
is performed. The gate interrupts any movement and this
alarm state
will be
signalled by the Blinker for 1 minute. The normal gate operations can be
restored by pressing any push button or radio commands.
If after the first safety strip obstacle detection, the safety strip is released and
then engaged again before the end of the gate travelling, the gate interrupts any
movement and this
alarm state
will be signalled by the Blinker for 1 minute. The
normal gate operations can be restored by pressing any push button or radio
commands.
The safety strip input (EDGE - COM) is a NORMALLY CLOSED contact.
In case there are more than one safety strip, all their contacts could be
connected in series.
In case the safety strip is not installed, this contact must be short
circuited with a wire jump (from EDGE to COM) to permit the gate to
operate.
PAY ATTENTION: it is highly recommended to check safety-strips
operation at least every 6 months.
TESTING THE SAFETY STRIP equipment (DIP12 ON)
The DIP12 ON enables the Test of safety strip equipment. The Test is
performed every time the gate completes a full opening. It is suitable only if the
safety strip device is equipped with a dedicated power supply input.
In fact, the safety strip equipment power supply input has to be connected to
the A+TEST and A- outputs (DIP12 ON). Automatically, every time the gate
completes a full opening, just before closing, the control board switches OFF
the A+TEST and A- power supply output for a very short time. While the safety
strip power supply is switched OFF, if everything is working fine the safety strip
contact (EDGE - COM) must open. In case the test fails, no other gate
manoeuvre will be allowed and the alarm state will be signalled by the Blinker
that will remain on.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH
DIP12 MUST BE LEFT OFF.
STOP BUTTON (COM-STOP)
During all the gate movement, the STOP button will stop the motor.
If it is pressed when the gate is still and completely open (or partially open in
the pedestrian position), automatic closing will be temporarily disabled even if
DIP3 is turned ON. Therefore, a new command will be needed to close the gate.
FLASHING LIGHT
Connect the flashing light to J1 flashing light outputs, use flashing lights
ACG7059 and bulbs of 40W maximum.
NOTE:
This electronic K board can only supply power to FLASHING LIGHTS
with inbuilt flashing circuit.
PRE-FLASHING function
The DIP8 in the ON position enables the pre-flashing, the FLASHING LIGHT
starts working 3 seconds before every movement of the gate.
The DIP8 in the OFF position disables any pre-flashing, the FLASHING LIGHT
and the motor will star at the same time.
OPEN GATE INDICATOR (SIGNAL-COM)
It indicates the gate status: open, partially open or not completely closed.
It switches off only when the gate is completely closed.
During programming, this indicator is active.
NOTE:
if button panels or bulbs are in excess, the electronic board logic will be
impaired and operations might stop.
PROBE
It’s a cable ended with a sensor to detect the motor temperature and, if
necessary, to active automatically the motor warming (code ACG4665).
T
ECHNICAL SPECIFICATIONS
- Humidity
< 95% without
condensation
- Power voltage
230V~ ±10% (120V/60Hz
upon request)
- Frequency
50/60Hz
- Maximum board absorption
30mA
- Interruptions in electricity supply
100ms
- Maximum load of open gate output
3 W (equal to 1 3W bulb or
to 5 LEDs connected in
series through a resistor of
from 2.2 kΩ)
- Blinking unit maximum output load
40W with resistive load
- Current available for photocells and accessories 400mA 24Vdc
- Current available on radio connector
200mA 24Vdc
- ALL THE PUSH BUTTONS, INPUTS AND COMMANDS CONNECTED TO
THE CONTROL BOARD MUST BE CLEAN CONTACT.