RHE28 Installation & Startup Guide – Doc. No. 8.2.1.07 – Ver. 1.31
23 / 43
ID
Abbreviation
Full Name / Description
[I-L01]
DigOutCh0/1/A/BConfig
Digital Output Channel 0 Configuration:
Alarm Channel configuration:
0: Error indication (default)
1: Mass flow alarm → set [I-L02, 03 & 04]
2: Volumetric flow alarm → set [I-L02, 03 & 04]
3: Density alarm → set [I-L02, 03 & 04]
4: Tube temperature alarm → set [I-L02, 03 & 04]
5: Torsion bar temperature alarm → set [I-L02, 03 & 04]
6: Pressure Alarm → set [I-L02, 03 & 04]
7: Forward Mass Totalizer TotalMassFwd for Batch Mode → set [I-L02, 03 & 04]
8: Forward Volume Totalizer TotalVolFwd for Batch Mode → set [I-L02, 03 & 04]
9: Fatal errors or Zeroing force output low, else high.
10: Fatal errors or Zeroing force output high, else low.
For values 1 to 8, the ERR output is pulled high when the alarm condition specified
in DigOutCh0/1/A/BAlmType, DigOutCh0/1/A/B AlmLow, and DigOutCh0/1/A/B
AlmHigh becomes true.
[I-L02]
DigOutCh0/1/A/BAlmType
Digital Output Alarm Type:
Alarm Channel: Digital Alarm Type:
0: Setpoint alarm (hysteresis, default) – Alarm is indicated when the output is
higher than DigOutCh0AlmHigh and cleared when it returns below
DigOutCh0AlmLow.
1: Inband alarm – Alarm is indicated when the output is in the range from
DigOutCh0AlmLow to DigOutCh0AlmHigh.
2: Outband alarm – Alarm is indicated when the output is outside the range
DigOutCh0AlmLow and DigOutCh0AlmHigh.
An indicated alarm on channel 0 pulls the digital output 4 labeled “ERR” low.
[I-L03]
DigOutCh0/1/A/BAlmLow
Digital Output Alarm Low:
Alarm low value, see DigOutCh0/1/A/B AlmType. Must be a floating point value of
0.0 or higher. There is no unit conversion for this register. The unit depends on the
DigOutCh0/1/A/B Config setting:
1: kg/min
2: m
3
/min
3: kg/m
3
4: Degrees Celsius
5: Degrees Celsius
6: Pascal
7: kg
8: m^3
The same units are used for all digital status outputs 0, 1, A, and B depending on
DigOutCh0/1/A/BConfig respectively.
[I-L04]
DigOutCh0/1/A/BAlmHigh
Digital Output Channel 0 Alarm High:
Alarm high value, see DigOutCh0/1/A/BAlmType. Must be a floating point value of
0.0 or higher. See DigOutCh0/1/A/BAlmLow for the unit specification.