Rh eo n i k M esst ech n i k
RE V . L O ct o b er 2014
.
RHEONIK Coriolis Flowmeter
Operation Manual RHE 07, 08, 11
Page
34
The configuration of the digital outputs and inputs has to be done in the standard menu
under
Setup I/O =>> Dig.
In1
(Input 1) can be configured as
Batch Start
or
Batch Stop.
In2
(Input 2) can be configured as
Batch Start
or
Batch Stop.
The function of
Out active=clsd
or
open
has no effect for the batch functions
(always setup as
active clsd
).
The valve is therefore always closed if there is a power failure on the batch system.
Preset
and
Prewarn-
outputs have the status off, if the valves are open. The Error output
has the status
off
, if there is no error!
Out1
(output 1) can be configured
Preset
or
Prewarn
(or standard function)
Out2
(output 2) can be configured
Preset
or
Prewarn
(or standard function)
Out3
(output 3) can be configured
Preset
or
Prewarn
(or standard function)
6.3. Option code selection
Choose in the service and diagnosis menu the sub-menu-step
Calibration Menu
.
Now press all 3 buttons in the same time.
The Display shows "
Option= 0.00000
"
Press the + or – button to select the needed code.
If you can see the right codes please press the
Next
button
and the chosen option is
active now.
If activated - switch off the batch function with code "
Option = 0.00005
", go out of the
menu and start the same procedure again.
with "
Pass = 0.02808
" you can chose TWO STAGE BATCH function with
Preset
and
Prewarn
without automatic overflow control "aoc".
or with "
Pass = 0.02809
" you can chose SINGLE STAGE BATCH function with just
Preset
and automatic overflow control "aoc" (
Prewarn
will be set automatically).