B. HOOK-UP
To wire unit, refer to the following hook-up diagram.
Refer to Figure 1 for location of wiring entrances.
Wiring to be done in the field between the unit and devices not attached to the unit, or
between separate devices which are field installed and located, shall conform with the
temperature limitation for Type T wire [63°F rise (35°C)] when installed in accordance
with the manufacturer’s instructions.
SINGLE STAGE COOL W/O
ECONOMIZER
MAPLE CHASE - MODEL #0970
HONEYWELL - MODEL #T8602C
MAPLE CHASE - MODEL #0960
WHITE RODGERS - MODEL #1F91-59
ROBERTSHAW - MODEL #CM64A-USAJ
TWO STAGE COOL W/
ECONOMIZER
HONEYWELL - MODEL #T7300-A1005
HONEYWELL - MODEL #T874D-1959
*
*
L2 connection 3Phase only
C. INTERNAL WIRING
IMPORTANT:
Some single phase units are equipped with a single pole contactor.
Caution must be exercised when servicing as only one leg of the power supply is broken
with the contactor.
A diagram of the internal wiring of this unit is located under the electrical box cover and
in this manual. If any of the original wire as supplied with the appliance must be
replaced, the wire gauge and insulation must be same as original wiring.
Transformer is factory wired for 230 volts on 208/230 volt models and must be changed
for 208 volt applications. See unit wiring diagram for 208 volt wiring.
D. THERMOSTAT
The room thermostat must be compatible with the spark ignition control on the unit.
Generally, all thermostats that are not of the “current robbing” type are compatible with
the integrated furnace control. The low voltage wiring should be sized as shown in Table
7.
Install the room thermostat in accordance with the instruction sheet packed in the box
with the thermostat. Run the thermostat lead wires inside the blower compartment and
connect to low voltage terminals as shown on the wiring diagram. Never install the ther-
mostat on an outside wall or where it will be influenced by drafts, concealed hot or cold
water pipes or ducts, lighting fixtures, radiation from fireplace, sun rays, lamps, televi-
sions, radios or air streams from registers. Refer to instructions packed with the thermo-
stat for “heater” selection or adjustment.
The following is a list of recommended thermostats to be used with or without an econo-
mizer:
Summary of Contents for RRNA-B SERIES
Page 46: ...46 FIGURE 24 WIRING DIAGRAM...
Page 47: ...47 FIGURE 25 WIRING DIAGRAM...
Page 48: ...48 FIGURE 26 WIRING DIAGRAM...
Page 49: ...49 FIGURE 27 WIRING DIAGRAM...
Page 50: ...50 FIGURE 28 WIRING DIAGRAM...
Page 51: ...51 FIGURE 29 SYSTEM CHARGE CHARTS 2 TON COOLING 13 SEER...
Page 52: ...52 FIGURE 30 SYSTEM CHARGE CHARTS 2 5 TON COOLING 13 SEER...
Page 53: ...53 FIGURE 31 SYSTEM CHARGE CHARTS 3 TON COOLING 13 SEER...
Page 54: ...54 FIGURE 32 SYSTEM CHARGE CHARTS 3 5 TON COOLING 13 SEER...
Page 55: ...55 FIGURE 33 SYSTEM CHARGE CHARTS 4 TON COOLING 13 SEER...
Page 56: ...56 FIGURE 34 SYSTEM CHARGE CHARTS 5 TON COOLING 13 SEER...
Page 58: ...58 FIGURE 36 15 SECOND PREPURGE...
Page 59: ...59...
Page 60: ...60 CM 1005...