Rheem RPVE Series Installation, Operation & Maintenance Instructions Manual Download Page 19

19

R e s i d e n t i a l   S p l i t

R e v. :   1 3   M a r c h ,   2 0 1 5

Refrigeration Installation

FP2 Sensor Installation

An FP2 sensor with violet wiring is shipped loose with the 
compressor section.  This is the air coil low temperature 
protection sensor.  Install this sensor on the refrigerant line 
between the indoor expansion valve and the air coil using 
thermal compound and the supplied mounting clips.  Ensure 
that the sensor makes good thermal contact with the refrigerant 
line and insulate the sensor.

Air coil low temperature protection will not be active if this 
sensor is installed incorrectly or is not installed.

Add-On Heat Pump Applications

The indoor coil should be located in the supply side of 
the furnace to avoid condensation damage to the furnace 
heat exchanger for add-on heat pump applications. A high 
temperature limit switch should be installed as shown 
in Figure 9b just upstream of the coil to de-energize the 
compressor any time the furnace is energized to avoid 
blowing hot air directly into the coil, elevating refrigerant 
pressures during operation. The heat pump will trip out on 
high pressure lockout without some method of disengaging 
the compressor during furnace operation. Alternatively, some 
thermostats with “dual fuel” mode will automatically de-
energize the compressor when second stage (backup) heat 
is required.

The TXV should be brazed into place as shown in Figure 8, 
keeping the “IN” side toward the compressor section. The 
TXV has an internal check valve and must be installed in the 
proper direction for operation. Always keep the valve body 
cool with a brazing shield and wet rags to prevent damage 
to the TXV. Attach the bulb to the suction line using the 
supplied hose clamp. Be careful not to overtighten the clamp 
and deform the bulb.

NOTICE!

 The air coil should be thoroughly washed with a 

fi

 lming agent, (dishwasher detergent like Cascade) to help 

condensate drainage. Apply a 20 to 1 solution of detergent 
and water. Spray both sides of coil, repeat and rinse 
thoroughly with water. 

Evacuation and Charging the Unit
LEAK TESTING -

 The refrigeration line set must be pressurized 

and checked for leaks before evacuating and charging the unit. 
To pressurize the line set, attach refrigerant gauges to the service 
ports and add an inert gas (nitrogen or dry carbon dioxide) until 
pressure reaches 60-90 psig [413-620 kPa]. Never use oxygen or 
acetylene to pressure test. Use a halogen leak tester or a good 
quality bubble solution to detect leaks on all connections made 
in the 

fi

 eld. Check the service valve ports and stem for leaks. If 

a leak is found, repair it and repeat the above steps. For safety 
reasons do not pressurize system above 150 psig [1034 kPa]. 
System is now ready for evacuation and charging.
Turn service valves full out CCW (see Table 6) and then turn 
back in one-half turn to open service ports. Add the required 
refrigerant so that the total charge calculated for the unit and 
line set is now in the system. Open the service valve fully 

counter clockwise so that the stem will backseat and prevent 
leakage through the schrader port while it is not in use. 
Start unit in the heating mode and measure superheat and 
subcooling values after 5 minutes of run time. See tables 
13a through 13d for superheat and sub-cooling values. 
Superheat is measured using suction temperature and 
pressure at the compressor suction line. Subcooling should 
be measured using the liquid line temperature immediately 
outside the compressor section cabinet and either the liquid 
line service valve pressure or the compressor discharge 
pressure. Note that di

 erent values from tables 13a through 

13d will be obtained due to the pressure losses through the 
condenser heat exchanger. Adding refrigerant will increase 
sub-cooling while superheat should remain fairly constant 
allowing for a slight amount of hunting in TXV systems. 
This increase in subcooling will require 5 minutes or so 
of operation before it should be measured. After values 
are measured, compare to the chart and go to “FINAL 
EVALUATION.”

PARTIAL CHARGE METHOD

 - Open service valve fully 

counterclockwise and then turn back in one-half turn to 
open service port. Add vaporized (Gas) into the suction side 
of the compressor until the pressure in the system reaches 
approximately 100-120 psig. Never add liquid refrigerant into 
the suction side of a compressor. Start the unit in heating 
and add gas to the suction port at a rate not to exceed 

fi

 ve pounds [2.27 kg] per minute. Keep adding refrigerant 

until the complete charge has been entered. Superheat is 
measured using suction temperature and pressure at the 
compressor suction line. Subcooling should be measured 
using the liquid line temperature immediately outside the 
compressor section cabinet and either the liquid line service 
valve pressure or the compressor discharge pressure. Note 
that di

 erent values from tables 13a through 13d will be 

obtained due to the pressure losses through the condenser 
heat exchanger. Adding refrigerant will increase sub-cooling 
while superheat should remain fairly constant allowing for 
a slight amount of hunting in TXV systems. This increase in 
subcooling will require 5 minutes or so of operation before it 
should be measured. After values are measured, compare to 
the chart and go to “FINAL EVALUATION.”

FINAL EVALUATION 

-In a split system, cooling subcooling 

values can be misleading depending on the location of the 
measurement. Therefore, it is recommended that charging 
be monitored in the heating mode. Charge should be 
evaluated by monitoring the subcooling in the heating mode. 
After initial check of heating sub-cooling, shut o

  unit and 

allow to sit 3-5 minutes until pressures equalize. Restart unit 
in the cooling mode and check the cooling superheat against 
Tables 13a through 13d. If unit runs satisfactorily, charging 
is complete. If unit does not perform to speci

fi

 cations the 

cooling TXV (air coil side) may need to be readjusted (if 
possible) until the cooling superheat values are met. 

Summary of Contents for RPVE Series

Page 1: ...er Quality Standards 14 Refrigeration Installation 15 22 Lineset Information 15 Hot Water Generator 23 25 HWG Module Refrigeration Installation For Outdoor Compressor Section Only 26 27 Electrical Lin...

Page 2: ......

Page 3: ...CKEL HEAT EXCHANGER EFFICIENCY REFERENCE 0 3 6 J C C N N 4 9 10 11 12 13 V 27 EER RETURN AIR FLOW CONFIGURATION VOLTAGE S SPLIT INDOOR CONFIGURATION HEAT EXCHANGER OPTIONS SUPPLY AIR FLOW MOTOR CONFIG...

Page 4: ...nts If a compressor is removed from this unit refrigerant circuit oil will remain in the compressor To avoid leakage of compressor oil refrigerant lines of the compressor must be sealed after it is re...

Page 5: ...autions must be taken to avoid physical damage to the units and contamination by foreign material Physical damage and contamination may prevent proper start up and may result in costly equipment clean...

Page 6: ...ler Matches for ARI Ratings Compressor Section 025 036 048 062 Air Handler Model RHPL HM2421 RHPL HM3621 RHPL HM24 RHPL HM6024 Refrigerant HFC 10A Metering Device TXV Non Bleed required Air Coil Type...

Page 7: ...er electrical and line set connections Any access panel screws that would be di cult to remove after the unit is installed should be removed prior to setting the unit Refer to Figure 1 for an illustra...

Page 8: ...TEN or leaks may occur The female locking ring is threaded onto the pipe threads which holds the male pipe end against the rubber gasket and seals the joint HAND TIGHTEN ONLY DO NOT OVERTIGHTEN Intern...

Page 9: ...30 Head ft GPM Speed 1 Speed 2 Speed 3 Figure 6 Pump Curves for RPVE internal pump s Double Pump 0 0 5 0 10 0 15 0 20 0 25 0 30 0 35 0 0 5 10 15 20 25 30 35 Head ft GPM Speed 1 Speed 2 Speed 3 CAUTION...

Page 10: ...ic pressure will fluctuate with the seasons Pressures will be higher in the winter months than during the cooling season This fluctuation is normal and should be considered when charging the system in...

Page 11: ...freeze 10 F 12 2 C set point and avoid nuisance faults see Low Water Temperature Cutout Selection in this manual NOTE Low water temperature operation requires extended range equipment Ground Loop Heat...

Page 12: ...xpansion tank should be sized to provide at least one minute continuous run time of the pump using its drawdown capacity rating to prevent pump short cycling Discharge water from the unit is not conta...

Page 13: ...ating valves should never be used with this equipment CAUTION Figure 6 Water Well Connections CAUTION Many units are installed with a field supplied manual or electric shut o valve DAMAGE WILL OCCUR i...

Page 14: ...304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maximum velocity of 1 8...

Page 15: ...Installing the Line set at the Compressor Section Braze the line set to the service valve stubs as shown in Figure 7 Remove the schraeder cores and heat trap the valves to avoid overheating and damag...

Page 16: ...ING WARNING If at all possible it is recommended that a new line set be used when replacing an existing R 22 system with an HFC 410A system In rare instances where replacing the line set is not possib...

Page 17: ...tdoor unit If the unit is operational follow steps F L F First start the existing R 22 system in the cooling mode and close the liquid line valve G Completely pump all existing R 22 refrigerant into t...

Page 18: ...d valve on the cylinder in this case keeping the cylinder upright 14 Once the liquid refrigerant has been completely recovered switch the recovery machine to vapor recovery so that the R 22 vapor can...

Page 19: ...calculated for the unit and line set is now in the system Open the service valve fully counter clockwise so that the stem will backseat and prevent leakage through the schrader port while it is not in...

Page 20: ...ng 1 Measure the temperature of the liquid line on the smaller refrigerant line liquid line just outside of the cabinet This location will be adequate for measurement in both modes unless a significan...

Page 21: ...ressor Section Insulated Linesets Low Voltage Air pad or Extruded polystryene PVC Condensate with vented trap Power Disconnects Compressor Section TXV IN toward Compressor Section PVC Condensate with...

Page 22: ...eady for charging If the system meets the requirements in Figure 10 it is ready for charging Figure 10 Evacuation Graph Charging The System There are two methods of charging a refrigerant system One m...

Page 23: ...For example consider the amount of heat that can be generated by the HWG when using the 125 F set point versus the amount of heat that can be generated by the HWG when using the 150 F set point In a t...

Page 24: ...SETPOINT MUST ONLY BE USED ON SYSTEMS THAT EMPLOY AN APPROVED ANTI SCALD VALVE PART NUMBER AVAS4 AT THE HOT WATER STORAGE TANK WITH SUCH VALVE PROPERLY SET TO CONTROL WATER TEMPERATURES DISTRIBUTED T...

Page 25: ...water piping with no less than 3 8 10mm wall closed cell insulation 3 Open both shut o valves and make sure the tank drain valve is closed Water Tank Refill 1 Close valve 4 Ensure that the HWG valves...

Page 26: ...ection and the refrigerant line connections on the HWG Maximum length should be 30 feet one way Evacuate the lineset to 500 microns through the hot gas valves in the outdoor unit Open the HWG valves i...

Page 27: ...igure 13d HWG Bypass Valve Figure 15 HWG Wiring Valve Open HWG Bypassed Valve Closed HWG Activated Control Board Circulator HWG Water Out HWG Refr Out HWG Refr In High Voltage HWG Water In TO RELAY R1...

Page 28: ...rify transformer tap with air handler wiring diagram to insure that the transformer tap is set to the correct voltage 208V or 230V CAUTION Use only copper conductors for field installed electrical wir...

Page 29: ...Voltage Field Wiring ELECTRICAL HWG WIRING Figure 18 HWG Module Wiring For Use with Outdoor Compressor Section TO RELAY R1 IN COMPRESSOR SECTION CONDENSER CONDENSER HWG Module Electrical Line Voltage...

Page 30: ...rature associated with thermistor FP1 Note that the FP1 thermistor is located on the refrigerant line between the coaxial heat exchanger and expansion device TXV Therefore FP1 is sensing refrigerant t...

Page 31: ...tion Since the unit will operate on first stage 80 90 of the time significant water savings can be realized by using two parallel solenoid valves with two flow regulators In the example above stage on...

Page 32: ...plate to the wall Thermostat wire must be 18 AWG wire Wire the appropriate thermostat as shown in Figures 26 through 30 to the low voltage terminal strip on the CXM control board Practically any heat...

Page 33: ...gure 28 Typical Two Stage Thermostat Heat Pump with Electric Heat Using A Humidistat for Dehumidification Figure 29 Typical Two Stage Thermostat Heat Pump with Electric Heat Using A Two Stage Thermost...

Page 34: ...o the following 1 A steady t appears on the ICC diagnostic display 2 The compressor and low speed pump outputs will be activated 3 The compressor and pump outputs will turn o after 5 seconds Note If a...

Page 35: ...ay of one 1 second for each stage of heating or cooling The Blower control has an on o indoor blower delay for heating and cooling The ICC ignores the low pressure control for the first 120 seconds of...

Page 36: ...0 continuous seconds three 3 times during the same command for compressor operation the ICC will lockout the compressor to keep it from continuing to operate and flash a L on the dual 7 segment LEDs f...

Page 37: ...n occurs Active Protection Code L7 Compressor Open Run Circuit If the ICC detects current in the start circuit without current present in the run circuit the ICC will lockout the compressor to keep it...

Page 38: ...more than 18 hours Low refrigerant charge Air ducts have substan tial leakage Dirty air filter or air coil 02 High Side Fault Compressor limit has opened four 4 times within a call for operation Dirty...

Page 39: ...30 Fuse Open The ICC detects the on board fuse is open The 3 amp fuse on the ICC is open Low voltage wiring at R and C is damaged or miswired 80 Low Air Flow The ICC detects that the blower is not pr...

Page 40: ...Stage Compressor Fan 1st Stage Pump Stage 2 Heating Y1 Y2 G 2nd Stage Compressor Fan 1st 2nd Stage Pumps Stage 3 Heating Y1 Y2 W1 W2 G 2nd Stage Compressor Fan 1st 2nd Stage Pumps Auxiliary Heat Emer...

Page 41: ...41 Residential Spl i t Rev 13 M arch 2015 ICC Controls Table 9 Nominal resistance at various temperatures Temp C Temp F Temp C Temp F Resistance kOhm Resistance kOhm...

Page 42: ...1 5 to 3 0 gpm ton 1 6 to 3 2 l m per kW Cooling Heating Air Limits Min ambient air DB 10 F 23 C 10 F 23 C Rated ambient air DB 80 6 F 27 C 68 F 20 C Max ambient air DB 110 F 43 C 85 F 29 C Min enter...

Page 43: ...slag and strong chemical cleaning agents Some antifreeze solutions may require distilled water Flow Controller pump s Verify that the pump s is wired purged of air and in operating condition System c...

Page 44: ...compare to Tables 13a through 13d Verify correct water flow by comparing unit pressure drop across the heat exchanger versus the data in Table 11 Heat of extraction HE can be calculated and compared...

Page 45: ...of Rejection Heat of Extraction 30 F 50 F 70 F 90 F 100 F 30 F 50 F 70 F 90 F 025 1 3 5 5 8 7 0 600 24 4 24 6 24 7 24 1 24 4 24 5 23 1 23 3 23 4 22 0 22 3 22 4 21 5 21 7 21 8 9 5 10 0 10 2 13 5 14 2 1...

Page 46: ...135 123 133 122 132 245 265 227 247 208 228 13 18 13 18 14 19 19 24 18 23 16 21 20 9 22 9 15 6 17 6 10 2 12 2 20 26 20 26 20 26 93 103 98 108 103 113 289 309 295 315 301 321 7 12 7 12 7 12 5 10 5 10 5...

Page 47: ...he water coil and may need more frequent inspections In areas with extremely hard water a HWG is not recommended Filters Filters must be clean to obtain maximum performance Filters should be inspected...

Page 48: ...at also has a wide range of fault and history information Sensor Inputs All sensor inputs are paired wires connecting each component to the board Therefore continuity on pressure switches for example...

Page 49: ...history Refer to mechanical troubleshooting No No No Yes Yes Yes No No No Yes Yes Yes Compressor control 7 segment lit Check control voltage to control Y1 LED lit Check thermostat wiring Flashing c o...

Page 50: ...water temp within design parameters X X Bad thermistor Check temp and impedance correlation per chart FP2 fault Code 86 X Reduced or no Air flow Check for dirty air filter and clean or replace Air Coi...

Page 51: ...eplace in heating Check fan motor operation and airflow restrictions Too high of external static Check static vs blower table X Reduced or no water flow Check pump operation or valve operation setting...

Page 52: ...035 6625 6 7 21 5 1 5 6 7 21 2035 6625 6 7 21 RROLQJ H SDQVLRQ YDOYH PHWHUV LQ WKH FRROLQJ PRGH DQG E SDVVHV LQ WKH KHDWLQJ PRGH HDWLQJ H SDQVLRQ YDOYH PHWHUV LQ WKH KHDWLQJ PRGH DQG E SDVVHV LQ WKH F...

Page 53: ...RI WKH IDLOXUH RI VXFK SRUWLRQ RU FRPSRQHQW 3URGXFWV RQ ZKLFK WKH XQLW LGHQWL FDWLRQ WDJV RU ODEHOV KDYH EHHQ UHPRYHG RU GHIDFHG 3URGXFWV RQ ZKLFK SD PHQW WR 0DQXIDFWXUHU RU WR WKH RZQHU V VHOOHU RU L...

Page 54: ...HPRYHG RU GHIDFHG 3URGXFWV RQ ZKLFK SD PHQW WR 0DQXIDFWXUHU RU WR WKH RZQHU V VHOOHU RU LQVWDOOLQJ FRQWUDFWRU LV LQ GHIDXOW 3URGXFWV VXEMHFWHG WR LPSURSHU RU LQDGHTXDWH LQVWDOODWLRQ PDLQWHQDQFH UHSDLU...

Page 55: ...55 Residential Spl i t Rev 13 M arch 2015 Notes...

Page 56: ...ch product at the time for order may be changed without notice and may not be as described herein Please contact the Manufacturer s Customer Service Department at 1 405 357 0409 for specific informati...

Reviews: